Meeting Pulse Tachometer Specifications (Vector Regulation Only); Verifying Power Module Output Current Rating Is Greater Than Motor Full Load Amps; Table 3.9 A C Input Line Fuse Selection Values - Reliance electric GV3000 Instruction Manual

A-c power modules
Hide thumbs Also See for GV3000:
Table of Contents

Advertisement

Model Number
1V4150
1V4450
2V4150
2V4450
3V4150
3V4450
5V4150
5V4450
7V4150
7V4250
10V4150
10V4250
15V4150
15V4250
20V4150
20V4250
25G4150
25G4250
25V4150
25V4250
30V4150
30V4250
40V4150
40V4250
50V4150
50V4250
50R4150
60G4150
60G4250
75R4150
125R4150
*Recommended fuse type: UL Class J, 600V, time delay, or equivalent.

3.2.4 Meeting Pulse Tachometer Specifications (Vector Regulation Only)

GV3000 drives set up for vector regulation require a pulse tachometer for closed loop operation.
Pulse tachometer specifications are provided in table A.6. Drives set up for volts/hertz regulation do
not require a pulse tachometer for feedback because they operate in the open loop mode.
3.2.5 Verifying Power Module Output Current Rating is Greater Than Motor Full Load
Amps
Verify that the GV3000 output current rating is greater than the motor's full load current (amps).
Table 2.1 lists the output current values.
3 8
Downloaded from StockCheck.com

Table 3.9 A C Input Line Fuse Selection Values

Horsepower Rating
1
2
3
5
7.5
10
15
20
25
25
30
40
50
Vector 50
V/Hz 75
60
Vector 60 75
V/Hz 100
Vector 100 125
V/Hz 125 150
Input Voltage
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
380 460 VAC
Fuse Rating*
6A
8A
12A
20A
25A
35A
45A
60A
70A
70A
100A
100A
125A
125A
150A
125A
150A
250A