Reliance electric GV3000 Instruction Manual page 58

A-c power modules
Hide thumbs Also See for GV3000:
Table of Contents

Advertisement

Terminal
Number
12
Isolated Reference
Voltage (+15VDC)
13
Analog Speed/Torque
Reference Input Voltage
(+/- 10 VDC)
14
Analog Speed/Torque
Reference Input Current
(0 20mA)
15
Isolated Speed/Torque
Reference Common
(Voltage/Current)
Downloaded from StockCheck.com
Table 7.1 Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring Analog Speed Reference Inputs
Parameters/Wiring Connections
The following parameters must be set:
P .000: Control Source
P .009: Terminal Strip Analog Input Offset
P .010: Terminal Strip Analog Input Gain
P .011: Terminal Strip Analog Input Invert
Refer to the GV3000 Programming instruction manual
(D2 3339) for additional parameter information.
Jumper J4 must also be set. See figure 2.10.