Digital Input Connections (Terminals 16 25)
Terminal 16: +24 VDC (Current Limited) (For remote control digital inputs only)
Terminal 17: Digital Input 8 (Remote/Local) Programmable
Terminal 18: Digital Input 7 (Ramp1/Ramp2) Programmable
Terminal 19: Digital Input 6 (Forward/Reverse) Programmable
Terminal 20: Function Loss
Terminal 21: Run/Jog
Terminal 22: Reset
Terminal 23: Stop
Terminal 24: Start
Terminal 25: +24 VDC Common
When a user installed function loss input, a coast to stop pushbutton, or another external interlock is
installed, the factor installed jumper connecting terminals 16 and 20 (or 16A and 20A) must be
removed so that a contact will open to stop the drive.
Terminals 17, 18, and 19 (remote control inputs 8, 7, and 6) are programmed using parameters P .007,
P .008, and P .031 through P .038. Factory default settings are shown here in parentheses. Refer to the
GV3000 Programming Manual (D2 3339) for more information.
Snubber Resistor Braking Connections (Terminals 26 and 27)
Terminal 26: Snubber Resistor Braking Signal (1 25HP Drives only)
Terminal 27: +24 VDC Common
Status Relay Connections (Terminals 28 31)
Terminal 28: N.C Relay Contact
Terminal 29: N.C. Relay Common
Terminal 30: N.O. Relay Contact
Terminal 31: N.O. Relay Common
Relay contact closure is programmable through parameter P .013. Refer to the GV3000 Programming
Manual (D2 3339) for more information.