Terminal
Number
19
Digital Input 6
(Default Forward/Reverse)
7 12
Downloaded from StockCheck.com
Table 7.1 Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring a Forward/Reverse Input
Parameters/Wiring Connections
Digital input 6 is control function programmable through
parameter P .007. The following parameters must be set:
P .000: Control Source
P .006: Second Menu Password
P .007: Terminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs 6
to 8).
P .008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or
Preset Speeds)
P .027: Reverse Disable
Note that based on the settings of parameters P .000, P .007,
P .008, and r.030 if an RMI board is used, the following
parameters can affect digital input 6.
P .023: MOP Accel/Decel Time
P .024: MOP Reset Configuration
P .031 to P .038: Preset Speeds 1 8
Refer to the GV3000 Programming instruction manual
(D2 3339) for additional information.
Terminal 19 On = Reverse Direction
Diagram shows factory setting. From the pulse tachometer
end of the motor, clockwise rotation indicates forward mo
tor movement.