Machine Positioning, Recessed Version - AERMEC DMH Installation Manual

Dehumidifier for radiant air conditioning systems
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 23
ATTENTION:
— The installation must be carried out inside the buildings.
— Leave a gap of at least 50 cm on the hydraulic and electrical connections side
and preserve accessibility for future maintenance or repairs. ensure possibly
free suction.
— With the purpose of favouring the regular flow of condensate, it is advised to
mount the unit inclined by 3 mm towards the condensate drain.
Grid locking bush
Electrical connections
Condensate drain
Hydraulic connections
ATTENTION:
— The installation must be carried out inside the buildings.
— Provide all the necessary holes for the passage of chilled water pipes, conden-
sate draining and electric cables.
— Leave at least 150 cm at the front to ensure the dehumidified air can freely cir-
culate.
21.10 – 5899000_03
tie-rod
nut
vibration damper
washer
bracket
washer
nut
nut
Grid locking bush
Outer casing
1

MACHINE POSITIONING, RECESSED VERSION

— We recommend positioning the unit at about 15-20 cm from the ground.
— Hydraulic and drainage connections are located near the gap of the unit, which
allows for rear, side or bottom connections.
— If the outer casing is supplied, it must be walled up beforehand in the recess,
leaving the holes to let the pipes and electrical cables through on the required
side. If necessary, drill a hole in the wall to discharge the overall dimensions of
the bush-holder inserts used to lock the front grid, fig. (1).
Assembly sequence
1. Apply the angular fastening element supplied with the outer casing on the
side of the machine, on the connections side.
2. Insert the unit into the outer casing, locking it at the back via the angular ele-
ment, using the self-tapping screws supplied, (fig. 2).
3. Ensure all the electrical connections pass inside the machine from the holes
under the control panel and go ahead with the internal connections.
4. Reconnect the electrical connectors and lock the door of the electrical control
board to its panel.
5. Centre the covering grid on the front bushes with the slotted holes on the grid
itself. Lower the grid until it is fully engaged on the bushes and bring the bot-
tom close to the flange of the outer casing, on which it will be locked due to the
action of a small magnet (fig. 3).
Fastening angular element
Compressor
Bush slot
Magnet
Fan
2
3
11

Advertisement

Table of Contents
loading

Table of Contents