Error
Description
Code
510
CTI Data Cache Client: Host
PLC Fatal Error
515
CTI Data Cache Client: Host
PLC in Program Mode
520
CTI Data Cache Client:
Inaccessible PLC Address
525
CTI Data Cache Client: No
Memory Buffers Available
for Data Write to Host PLC
(too many Write requests
during one Host PLC scan).
540
CAMP Client Error
(Connection to servers or
communication failed)
550
MODBUS Client Error
(Connection to servers or
communication failed)
560
Data Exchange Error
(Subscriber not receiving
data from one or more
Publishers).
570
Ethernet/IP Scanner Error
(Connection to servers or
communication failed)
580
Ethernet/IP Tag Client Error
(Error is default at startup
when configured)
590
MQTT Client Error
(Connection to broker or
communication failed)
595
NTP Server Error
(Connection to NTP Server
lost/failed)
* Not displayed on Alphanumeric Display
CTI Janus Programmable Automation Controller IOG
Priority
Operation
26
Controller continues to run
normally
29
Controller continues to run
normally
29
Controller continues to run
normally
*
Controller continues to run
normally.
Error clears next IEC PLC
cycle.
28
Controller continues to run
normally
28
Controller continues to run
normally
27
Controller continues to run
normally
28
Controller continues to run
normally
28
Controller continues to run
normally
28
Controller continues to run
normally
28
Controller continues to run
normally
Error Recovery
Clear Host PLC Fatal Error
Change Host PLC mode to RUN
Check that CTI Data Cache
configuration matches PLC
memory configuration
Increase Host PLC time slice for
CTI Data Cache interface.
Set "fixed" IEC PLC cycle time.
Check configuration and
connection to CAMP Server(s).
Check configuration and
connection to Modbus Server(s).
Check Global Binding
configuration and connection to
Data Exchange Publisher device.
Check configuration and
connection to EIP Adapter(s).
Check configuration and
connection to EIP Server.
Check configuration and
connection to MQTT broker.
Check configuration and
connection to NTP Server.
67
Need help?