Execution Errors
Error
Description
Code
310
System Exception Error
(Detected after CPU reset
following Segmentation
Fault or Firmware Error)
320
System Watchdog Timeout
(Detected after CPU reset
following Segmentation
Fault or Firmware Error)
330
Program Logic Error
SD Card Errors
Error
Description
Code
350
Internal SD Card Disk Full
(no further writes to internal
SD card)
355
Internal SD Card Free Space
Limit
(disk > 90% full)
360
Internal SD Card Free Space
Warning
(disk > 80% full)
370
Front Panel SD Card Not
Accessible (Missing,
Incompatible, Unformatted
or Write-Protected)
64
Priority
Operation
6
System restarts.
Controller remains
stopped after restart.
7
System restarts.
Controller remains
stopped after restart.
7
Controller enters ERROR
state (Logic programs and
fieldbus protocols are
stopped).
Priority
Operation
15
Controller continues to
run, but database updates,
user file functions, and
program downloads are
prohibited.
16
Controller continues to
run, but all user file access
functions are disabled
(should return errors when
called).
17
Controller continues to run
normally.
16
Controller continues to run
normally
CTI Janus Programmable Automation Controller IOG
Error Recovery
Connect Workbench and transfer
to RUN or use C
E
LEAR
XCEPTION
button to restart CPU.
Contact CTI Support.
Connect Workbench and transfer
to RUN or use Reset button to
restart CPU.
Contact CTI Support.
This condition most likely caused
by 'Infinite Logic Loop' or 'Bad
Array Index'. Connect Workbench
to correct problem and transfer to
RUN or use 'Clear Exception'
button to restart CPU.
Error Recovery
Use Web Server
'SD Card File Management' page
to transfer or delete user files.
Use Web Server
'SD Card File Management' page
to transfer or delete user files
Use Web Server
'SD Card File Management' page
to transfer or delete user files
Cancel function that is using
Front Panel SD Card, or correct
problem with SD card.
Need help?
Do you have a question about the Janus CTI 2500C-J Series and is the answer not in the manual?