Page 1
CTI 2500-RIO-B RS485 REMOTE BASE CONTROLLER INSTALLATION AND OPERATION GUIDE Version 1.4 2500-RIO-B-IOG/04242018...
Page 2
Every effort has been made to ensure the accuracy of this document; however, errors do occasionally occur. CTI provides this document on an “as is” basis and assumes no responsibility for direct or consequential damages resulting from the use of this document. This document is provided without express or implied warranty of any kind, including but not limited to the warranties of merchantability or fitness for a particular purpose.
Page 3
This Installation and Operation Guide provides reference information for the CTI 2500-RIO-B RS485 Remote Base Controller. The information in this manual is directed to individuals who will be installing the module and configuring it for use with a CTI 2500 Series® or Simatic® 505 Processor.
Page 4
Notes alert the user to special features or procedures. CAUTION: Cautions alert the user to procedures that could damage equipment. WARNING: Warnings alert the user to procedures that could damage equipment and endanger the user. CTI 2500-RIO-B Installation and Operation Guide V1.4...
Siemens® and CTI. The 2500-RIO-B RS485 Remote Base Controller (RBC) allows a 2500 Series® I/O base to function as a remote base. The 2500-RIO-B is intended to be a replacement for the Siemens® 505-6851-A RBC. It provides the following functions: ...
Appendix A. 1.3. Dual-Media and Hardware Redundancy Installations A pair of 2500-RIO-B RBC’s may be installed in a 2500-R11-A or 505-6511 redundant base to provide dual media as well as hardware redundancy. In a redundant configuration, two 2500-RIO-B units are installed in the base and separate cable runs are used to provide redundancy in both the hardware and communications cabling between the CPU and the remote base.
2500-TAP Figure 1: Typical Dual Media Redundancy Layout NOTE Only 2500-RIO-A or 2500-RIO-B controllers may be used in redundant or dual media applications. CTI RIO modules cannot be combined with Siemens 505-6851A or 505-6851B modules. NOTE For comprehensive remote I/O system design and installation information, you should also obtain the CTI 2500 Series®...
Belden 9182 150 ohms, 5%, ¼ W ® Belden 9860 or 9271 120 ohms, 5%, ¼ W The terminating resistor is installed between terminal numbers 3 and 8, the transmit and receive lines. CTI 2500-RIO-B Installation and Operation Guide V1.4...
Before proceeding, you must determine what address you will assign to the RBC. Remote Base addresses range from 1 to 15. In CTI 2500 Series® and Simatic® 505® systems, address 0 is reserved for the local base where the CPU is installed. Note that each Remote Base on the Remote I/O channel must have a unique address.
I/O base. CAUTION: The components on the 2500-RIO-B module printed circuit card can be damaged by static electricity discharge. To prevent this damage, the module is shipped in a special anti-static bag. Static control precautions should be followed when removing the module from the bag and when handling the printed circuit card during configuration.
Setting Remote Base Controller Station Address A thumbwheel switch is provided to set the base address to the 2500-RIO-B for Remote I/O station identification. A maximum of 15 remote bases can be connected to the CTI 2500 Series® CPU or Siemens®...
RBC pair is inoperative. This is normal – the CPU makes no attempt to communicate with the serial port of the standby RBC. The standby unit is the one displaying a “C” on the front panel LED display. CTI 2500-RIO-B Installation and Operation Guide V1.4...
2.7. Connecting the Remote I/O Cable The I/O Port connects the 2500-RIO-B to a SIMATIC® 505 compatible RS485 Remote I/O channel. This enables the remote CTI 2500 Series® or Simatic® 505® CPU to control the I/O modules in the base where the RBC is located.
2.8. Operation of LED Display The LED Display is used to indicate the status of the 2500-RIO-B Remote Base Controller as shown in the following table: Display Definition Communications Comment / Action to RBC Module Ready Fully Operational and online with CPU.
STW168 Dual RBC Status STW184 I/O module mismatch STW210 Remote I/O base poll enable flags Note: Addresses above STW242 are used only by CTI’s 2500 Series® CPU’s. STW455-461 Remote base receive errors STW471-485 Remote base abnormal logoff counts STW487-501 Remote base timeout counts More complete information and a list of the 2500 Series®...
The cable shield is used to improve the immunity to electromagnetic interference. The ideal cable provides low signal attenuation for long trunk lines and flexibility for ease of installation. The recommended cable should include the characteristics as shown in the following table. CTI 2500-RIO-B Installation and Operation Guide V1.4...
Page 19
CTI recommends Beldon 3105A cable for wiring remote I/O. The following table contains the general recommended cable specs for RS485 remote I/O wiring and the preferred Beldon cable type specifications. Cable Characteristic Recommended Belden® 3105A Conductors 18AWG to 22AWG uniform 2-conductors,22AWG,.030...
Page 21
1600 ft (488 m) 800 ft (244 m) 2400 ft (732 m) 1533 ft (476 m) 767 ft (234 m) 2300 ft (701 m) 1400 ft (427 m) 733 ft (223 m) 2200 ft (671 m) CTI 2500-RIO-B Installation and Operation Guide V1.4...
MUST be terminated at both ends with a terminating resistor approximating the characteristic impedance of the cable. For Belden® 3105A cable, a termination resistor value of 120 ohms should be connected across the TX/RX+ and TX/RX- signal lines. CTI 2500-RIO-B Installation and Operation Guide V1.4...
If this cannot be avoided, additional protective measures should be taken, such as laying the cables in a steel pipe or rugged metal duct. The pipe or duct should then be grounded at regular intervals and protected against corrosion. CTI 2500-RIO-B Installation and Operation Guide V1.4...
APPENDIX B. I/O “SAFE STATE” OPERATION The 2500-RIO-B Remote Base Controller is designed to place the I/O on its base into a “safe state” on the occurrence of various kinds of system failures involving the PLC processor and communications cabling. The safe state for the I/O depends on the setting of the FREEZE jumper (see Section 2.4).
Storage Temperature: -40º to 85º C (-40º to 185º F) Humidity: 5% to 95%, non-condensing Agency Approvals Pending: UL, ULC, CE, Class I Division 2 Hazardous Location Shipping Weight: 1.5 lb. (0.68 Kg) CTI 2500-RIO-B Installation and Operation Guide V1.4...
LIMITED PRODUCT WARRANTY For product Warranty information, please see our standard product warranty at http://www.controltechnology.com/support/warranty/ CTI 2500-RIO-B Installation and Operation Guide V1.4...
In the event that the Product should fail during or after the warranty period, a Return Material Authorization (RMA) number can be requested orally or in writing from CTI main offices. Whether this equipment is in or out of warranty, a Purchase Order number provided to CTI when requesting the RMA number will aid in expediting the repair process.
Need help?
Do you have a question about the 2500-RIO-B and is the answer not in the manual?
Questions and answers