I/O Subsystem Errors

Error
Description
Code
410
Local I/O Module Error
(module slot configuration
mismatch or module
failure).
415
Local I/O Interface Timeout
Error
(Local I/O Driver or FGPA
Interface Task watchdog
expired due to
communication timeout).
420
Remote I/O RBC Error
(One or more bases are
enabled but not exchanging
data with PLC.)
425
Remote I/O Module Error
(Module slot configuration
mismatch or module
failure).
430
Remote I/O Interface
Timeout Error
(Remote I/O Driver or FGPA
Interface Task watchdog
expired due to
communication timeout).
CTI Janus Programmable Automation Controller IOG
Priority
Operation
22
Controller continues to run
normally
14
'Output Disable' for Local
Base asserted. Controller
continues to run normally
21
Controller continues to run
normally
22
Controller continues to run
normally
14
'Output Disable' for RBCs
asserted. Controller
continues to run normally
Error Recovery
Ensure Local I/O configuration
matches I/O modules installed in
local base.
Local I/O Subsystem attempts to
recover automatically.
Reset PLC and contact CTI if
condition repeats.
Ensure RBC addresses and cabling
are correct.
Check Event Log for details.
Ensure RBC configurations match
I/O modules installed in bases.
Remote I/O Subsystem attempts
to recover automatically.
Reset PLC and contact CTI if
condition repeats.
65