CHAPTER 4
The following parameters can be configured via the embedded web server:

4.1 General Settings

Navigate to the C
ONFIGURATION
Module Identifier:
This is an optional text field that identifies the particular controller. If Enhanced Data Cache is configured, this
name will be displayed in the CTI 2500 Series PLC Host controller scan statistics.
Operation following Module Reset:
This selection determines how the application program will execute on startup following a power cycle.
Restore Last State: Restores application program to state it was in when power was lost. If the application
was running, it will be set to RUN mode with Hot Start initialization so that all variables are set to their last
value (default)
Application Stop: All logic programs and fieldbus drivers stopped
Auto-Run Cold Start: Starts application in RUN mode with all variables set to their initialization value
Auto-Run Warm Start: Starts in RUN mode with RETAIN variables are set to their last value and all other
variables are set to their initialization value
Auto-Run Hot Start: Starts in RUN mode with all variables are set to their last value
Operation following Project Download from Workbench:
Application Stop: All logic programs and fieldbus drivers are stopped
Logic Stop: All logic programs are stopped, fieldbus drivers execute (default)
Run: Application set to RUN mode – all logic programs and fieldbus drivers execute
Front Panel Display Items:
Check box to Display Primary Network IP address on front Panel (default is Enabled)
Check box to display configured Alternate Subnet IP addresses on front panel (default is Enabled)
Click on the APPLY button to apply settings. A confirmation message should be displayed indicating that the
parameters have been updated. New parameters will go into effect immediately
The "Display Alternate subnet IP addresses" option is available only when
.
CTI Janus Programmable Automation Controller IOG
/G
S
s web page.
ENERAL
ETTING
"Display Primary Network IP" is
CONFIGURATION
NOTE
enabled.