Download Print this page

Huawei FusionDC1000B Quick Manual page 88

Hide thumbs Also See for FusionDC1000B:

Advertisement

Category
System Settings
Settings
Input Settings
Output Settings
Parameter
Altitude (m)
Top outlet fan
Dust-proof maintenance period (d)
Intra-rack power mode
Block start delay (s)
Inter-rack power mode
Block start delay (s)
NTC
BCB trips if UPS stops power supply
Intelligent generator mode
Formula
Output voltage level (V)
Output volt. adjustment(V)
Output frequency (Hz)
Output freq. track rate (Hz/s)
EOD restart
EOD restart delay
Zero display with no load output
Calib. output current if no load
Default Value
≤ 1000
Disable
0
Depends on the default
number of power modules. The
default value is 2.0, 1.0, and
0.5 for 1–5, 6–10, and 10–20
power modules respectively.
5
Disable
Enable
Disable
400 V
The default value is 220.0,
230.0, and 240.0 when the
380V: 209.0–231.0; 400V: 218.5–
voltage level is 380 V, 400 V,
241.5; 415V: 228.0–252.0
and 415 V respectively.
50 Hz
0.6 Hz/s
Enable
10
Enable
Disable
Value Range
Setting
≤ 1000,
1000–2000,
2000–3000,
Default value
3000–4000,
4000–5000,
Enable/Disable
Disable
0–365
0
0.5–120.0
2
2–120
Default value
Enable/Disable
Disable
Enable/Disable
Disable
Enable/Disable
Disable
380 V, 400 V, 415 V
415 V
240
50 Hz, 60 Hz
50 Hz
0.1Hz/s–2.0Hz/s
0.6 Hz/s
Enable/Disable
Enable
1–1440
10
Enable/Disable
Enable
Enable/Disable
Disable
R
Remarks
e

Advertisement

loading