Initial Switch-On - Lenze i510 Operating Instructions Manual

Cabinet frequency inverter
Hide thumbs Also See for i510:
Table of Contents

Advertisement

Commissioning

Initial switch-on

Important notes
Additional functions
Initial switch-on
DANGER!
Unexpected states during commissioning
Incorrect wiring can cause unexpected states during the commissioning phase.
Possible consequences: Death, severe injuries, or damage to property
• Wiring must be complete and correct.
• Wiring must be free of short circuits and earth faults.
• The motor circuit configuration (star/delta) must be adapted to the inverter.
• The motor must be connected in-phase (rotating direction).
• The "emergency off" function of the overall system must operate correctly.
• Clear hazardous area.
• Observe safety instructions and safety clearances.
Preconditions:
• The power connections must be wired.
• The digital inputs X3/DI1 (start/stop), X3/DI3 (reversal) and X3/DI4 (frequency preset 20 Hz)
must be wired.
• The analog input X3/AI1 must not be wired or connected to GND.
1. Switch on mains voltage.
2. Check readiness for operation.
3. Observe LED status displays "RDY" and "ERR" on the inverter front panel.