11.4.24 Basic settings
The different settings are summarized with the Basic settings parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x50
1
0
R/W
2
1
R/W
3
2
R/W
4
3
R/W
Description of parameter values
Index name
Basic settings
Inversion of LED col-
On site initialization
IO-Link process data
www.gemu-group.com
Length
Index name
1 bit
Basic settings
1 bit
1 bit
1 bit
Parameter
Values
ours
Operating mode
Parameter
Type
Inversion of
Boolean
LED colours
On site
Boolean
initialization
Operating mode
Boolean
IO-Link process
Boolean
data
0
(Standard) LEDs Close = green and Open = yellow (not in-
versed).
1
(Inversed) LEDs Close = yellow and Open = green (inversed).
0
(Enabled) On-site initialization activated.
1
(Disabled) On-site initialization deactivated.
0
Operating mode for positioner activated.
1
Operating mode for OPEN/CLOSE control activated.
0
(Disabled) Use of IO-Link process data (see "Process data",
page 20) is deactivated.
1
(Enabled) Use of IO-Link process data (see "Process data",
page 20) is activated.
35 / 53
11 Specific data IO-Link (pin 6)
Default
Values
0
0
1
0
0
1
0
0
1
0
0
1
Description
GEMÜ Q50 eSyStep
Positioner (Code S0, S5, S6)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q50 esystepS0S5S6

Table of Contents