Configuration And Operation; Initial Start-Up; Control Elements - Kaco Blueplanet 87.0 TL3 Series Manual

Hide thumbs Also See for Blueplanet 87.0 TL3 Series:
Table of Contents

Advertisement

9

Configuration and operation

9.1

Initial start-up

NOTE
The DC power supply must be guaranteed during initial start-up.
The sequence of the settings required for initial start-up is preset in the configuration assistant.
9.2

Control elements

The 3 LEDs on the device show the different operating states. The LEDs can display the following states:
LED illuminated
Operating status
Start
Feed-in start
Feed-in operation with re-
duced power
Non-grid feed mode
Fault
Page 44
LED flashing
LED
Symbol
Description
The green LED "Operating" lights up if AC and DC voltage are present.
If the LED is flashing, internal communication between the components
is being established. When the LED stops flashing, the device is ready to
feed in.
If the LED continues to flash for a long time, there is an internal commu-
nication error.
The green "Operating" LED is illuminated.
The green "Feed-in" LED is illuminated after the country-specific wait-
ing period*.
The device feeds into the grid.
You can hear the circuit-breaker / interface switch switch on.
The green "Operating" LED is lit.
The green LED "Feed" is flashing because one of the modes: internal
power reduction, external power reduction, idle power request or stand-
alone mode is active.
The device feeds into the grid.
You can hear the circuit-breaker / interface switch switch on.
The green "Operating" LED is illuminated.
No LEDs are illuminated.
Fault in the device or AC/DC source
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
LED not illuminated
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3