Commissioning; Commission The Inverter; Set Inverter Address - Growatt MAX 80-150KTL3-X LV Series Installation & Operation Manual

Table of Contents

Advertisement

7. Commissioning

7.1 Commission The Inverter

•If the inverter is stored over one month, its default time
and date may looks wrong, the time and date should be
reset before connection to the grid.

7.1.1 Set inverter address

After inverter is started normally, inverter address can be set via RS485/USB
converting to WIFI. When multiple inverters are connected in parallel via RS485, the
inverter must be set to a different communication address. When a single inverter
communicates, the default communication address can be used.
Note: The default communication address of the inverter is 1, which can be set to
1-254.
7.1.1.1 Set RS485 address with Shinebus
The 485 address of the inverter can be modified by Shinebus, This operation is
performed by a professional.
7.1.1.2 Set RS485 address on ShinePhone APP
Refer to 8.2 download mobile APP ShinePhone and connect to inverter WIFI to enter
local monitoring page, this operation is performed by a professional.
1>Click "Parameters"
2>Enter password.(When you use it for the first time, you need to set the password
first. Click "Reset password" to enter the OSS account number and password. The
distributor and installer can apply for the OSS account from Growatt. Click "Sign in"
to set the password. After the setting is successful, you can start using it.)
3>Click top item "COM Address";
4>Click the "Read" button in the upper right corner to read the current
31 / 56
编号:GR-UM-C -00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Max 80-150ktl3-x mv series

Table of Contents