•Each inverter must install one AC breaker AC breaker is forbidden
to share with other inverters.
•It is forbidden to add load between inverter and breaker.
Preparation before connection:
1>Disconnect inverter DC switch and AC breaker or switch.
2>When you lock the AC cable's screw, the torque force should be 100kgf·cm.
When you lock the cover screw, the torque force should be 35kgf·cm.
3>Measure the grid voltage and frequency, please refer to chapter 10.
AC breaker specification:
MAX 100KTL3-X LV
MAX 110KTL3-X LV
MAX 120KTL3-X LV
MAX 125KTL3-X LV
MAX 133KTL3-X LV
MAX 125KTL3-X MV
MAX 136KTL3-X MV
MAX 150KTL3-X MV
AC wire specification:
Inverter Model
MAX 80KTL3-X
LV
MAX 100KTL3-X
LV
MAX 110KTL3-X
LV
MAX 120KTL3-X
LV
MAX 125KTL3-X
LV
MAX 133KTL3-X
LV
MAX 125KTL3-X
MV
MAX 136KTL3-X
MV
Inverter model
MAX 80KTL3-X LV
Copper wire
crosssectional
area(mm²)
70-240
70-240
70-240
70-240
70-240
70-240
70-240
70-240
Breaker model
160A/400Vac
200A/400Vac
200A/400Vac
200A/400Vac
250A/400Vac
250A/400Vac
200A/500Vac
200A/500Vac
200A/500Vac
Copper wire
recommendation(
mm²)
70
70
70
70
70
70
70
70
22 / 56
编号:GR-UM-C -00
Aluminum wire
recommendation(mm²)
95
95
95
95
95
95
95
95