Growatt MOD TL3-XH Series Installation & Operation Manual

Growatt MOD TL3-XH Series Installation & Operation Manual

Photovoltaic inverter

Advertisement

Growatt New Energy
Download
Manual
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,
Hangcheng Ave,Bao'an District, Shenzhen, China
T
+86 0755 2747 1942
E
service@ginverter.com
W
www.ginverter.com
GR-UM-246-A-02
Installation
&
Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MOD TL3-XH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Growatt MOD TL3-XH Series

  • Page 1 Installation & Operation Manual Growatt New Energy Download Manual Shenzhen Growatt New Energy Co., Ltd 4-13/F,Building A,Sino-German(Europe) Industrial Park, Hangcheng Ave,Bao’an District, Shenzhen, China +86 0755 2747 1942 service@ginverter.com www.ginverter.com GR-UM-246-A-02...
  • Page 2 Index 1 Notes on this manual 1.1 Validity Applicable personnel Symbols in this document 2 Safety 2.1 Product description and features 2.2 Qualification of skilled person 2.3 Safety instruction 3 Product overview Appearance overview Dimensions Storage environment 4 Unpacking inspection 5 Installation 5 1 Basic installation requirements 5.2 Mounting wall mount...
  • Page 3 13 Troubleshooting 7 Debugging 13 1 Error message 13 2 Syetem error 14 Manufacturer warranty 8 Working mode Normal mode Failure mode Shutdown mode 15 Decommissioning 9 OLED display and touch 15.1 Dismantling the inverter 9.1 Boot display 15.2 Packing the inverter buttons 9.2 OLED display wake up 15.3 Storing the inverter...
  • Page 4: Notes On This Manual

    Warnings indicate hazards to equipment or personnel. It draws your attention to a certain procedure or practice. If the procedure or practice is not properly implemented or Alternating Current (AC) followed, it may cause damage or destruction of part or all of the Growatt device and/or Read the manual Symbol Description CE mark.
  • Page 5: Product Description And Features

    Abbreviation for "Alternating Current” by photovoltaic panels into alternating current, and send it to the grid in a three-phase manner. Growatt MOD 3-10K TL3-XH series inverter can be connected to 2 strings , Abbreviation for "Direct Current” has 2 maximum power tracking point trackers, so suitable for connection 2 Set of Energy arrays of different panels.
  • Page 6: Qualification Of Skilled Person

    Persons with limited physical or mental abilities may only work installation and maintenance personnel; with the Growatt inverter following proper instruction and under 6.The use of this machine for grid-connected power generation requires constant supervision. Must keep the Growatt inverter away permission from the local power supply department;...
  • Page 7: Product Overview

    Product overview 2.3.3 Operation Warnings 3.1 Appearance overview Ø Ensure all connectors are sealed and secure during operation. Ø Although designed to meet all safety requirements, some parts and surfaces of inverter are still hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV-inverter or nearby surfaces while inverter is operating.
  • Page 8: Unpacking Inspection

    Unpacking inspection 3.2 Dimensions Before opening the inverter package,please check whether the outer package is damaged.After unpacking,please check whether the appearance of the inverter is damaged or lack of accessories.If there is damage or missing parts,please contact the dealer. Fig 3.2 Size and weight: Fig 4.1 Model...
  • Page 9: Installation

    Installation 5.1 Basic installation requirements Ø The wall on which the inverter is mounted must be sturdy and can withstand the weight of the inverter for a long time (refer to the specifications in Chapter 17 for the weight of the inverter); Ø...
  • Page 10: Install The Wall Mount

    5.2 Install the wall mount 5.2.1 Install the wall mount To prevent electric shock or other damage, be sure to check the wall for power or other piping before opening the hole in the wall. Danger Fig 5 7 Specifications of wall mount Secure the wall mount as shown, do not let the screws flush with the wall, instead Fig 5.4 Installation expose 2 to 4 mm.
  • Page 11: Inverter Wiring

    Inverter wiring 6.1 Security There may be a high voltage in the conductive part of the inverter, which may cause electric shock.Therefore, when installing the inverter,make sure that the AC and DC sides of the Danger inverter are powered off. Static electricity may damage the electronic components of the inverter.Anti-static measures should be taken during the replacement or installation of the inverter.
  • Page 12 AC connection steps : Preparation before wiring: 1.Pass the 5 wires (A,B,C,N and PE wires) through the AC shield,crimp the O/U Connect the protective ground wire (PE) terminal and connect to the screw terminals on the AC connector. Connect the inverter to the grounding bar through the protective earth (PE) to achieve grounding protection.
  • Page 13: Dc Side Wiring

    Note Model Wire cross-sectional area claims are void. MOD TL3-XH series 6mm :MAX40m The MOD series inverter has two independent inputs, as shown in the figure below: MOD 3-6KTL3-XH 6-8mm 8mm :MAX60m...
  • Page 14: Connect The Signal Cable

    6.4 Connecting the Bidirectional DC/DC Box 6.5 Connect the signal cable The MOD series inverter has an30-Pin signal connector except Vietnam models.The 6.4.1 Conditions for Bidirectional DC/DC Box client signal line port is as follows: MOD 3-10KTL3-XH single-phase inverter has one independent BAT input : BAT+/BAT- connecting to the output of Bidirectional DC/DC Box.
  • Page 15: Grounding The Inverter

    6.6 Grounding the inverter This series inverter has integrated export limitation functionality. To use this function, you can connect the Growatt smart meter. For the detailed information, please contact The inverter must be connected to the AC grounding conductor of the power with Growatt.
  • Page 16: Inverter Demand Response Modes (Drms)

    6.8 Inverter demand response modes (DRMS) 6.8.3 Using the Power Control Interface for EU This series inverter has the function of demand response modes, We use 16-Pin socket as inverter DRMS connection. DRMS application description Ø Applicable to AS/NZS4777.2:2015 or Commission Regulation (EU) 2016/631.
  • Page 17 Debugging 6.9 AFCI(Optional) 1.Close the DC switch on the inverter As long as the input DC voltage is greater than 140V,the inverter display will show the following information:No mains 6.9.1 Arc-Fault Circuit Interrupter (AFCI) connection error,the inverter LED will turn red. In accordance with the National Electrical Code R, Article 690.11, the inverter has a If other information is displayed,please refer to Chapter 13.If you encounter any system for the recognition of electric arc detection and interruption.
  • Page 18: Working Mode

    When the sunlight is weak or there is no sunlight,the inverter will automatically stop running.When in shutdown mode,the inverter basically does not consume energy from the grid or solar panels,and at the same time,the inverter's display screen and LED lights will be turned off. Growatt Country/Area Press Set OK...
  • Page 19: General Setting

    9.2 General setting 9.2.4 Set inverter time 9.2.1 Set inverter display language Double touch Double touch Double touch Double touch Time Setting Time Setting Time Setting Time Setting Set OK 20:05:00 NN:NN:00 20:05:00 NN:05:00 Double Single Single Single Single touch Language Language touch...
  • Page 20 9.3.1Export limitation setting The –XH series inverters can work in anti-backflow mode through external power meter or CT,the user can set the percentage of power allowed to flow backward Double touch Double touch General Reset Factory Set OK the OLED, Single touch to switch display or make the number 1.Double touch to Advanced confirm the setting, as described below: Double touch...
  • Page 21 9.3.6 Power derating for voltage variation (Volt-Watt mode) Double Double touch Double touch touch Double touch LoadFirst 00-01 LoadFirst 00-01 LoadFirst 00-01 LoadFirst 00-01 TimePeriod Set Time1: Disable Time1: Disable Time1: Disable Time1: Disable The inverter power output will vary in response to the AC grid voltage. This is switched Multiple single Multiple single Multiple single...
  • Page 22: Communication And Monitoring

    Maintenance and Cleaning Communication and Monitoring 10.1 RS485 11.1 Checking Heat Dissipation This series of inverters provide two RS485 ports. You can monitor one or more If the inverter regularly reduces its output power due to high temperature, please inverters via RS485. The other RS485 port is used to connect a smart meter (stand- improve the heat dissipation condition.
  • Page 23: Troubleshooting

    LED indicator red will light up. Faults include system faults and inverter faults. In some cases, you may be advised to contact Growatt, please provide the following Before turning the inverter on, please make sure the PV/Battery input voltage and information.
  • Page 24 Warning Warning Description Suggest Description Suggest message message 1.Unplug the U disk 1.Check if the meter is on U disk over-current 2.Re-access U disk after shutdown Warning 207 Warning 401 Meter abnormal 2.Check the machine and the meter connection protection 3.If the error message still exists, contact is normal.
  • Page 25 13.3 System error Error Description Suggest Error Description Suggest D C I b i a s 1.Restart inverter Error 400 abnormal 2.If error message still exists, contact manufacturer. 1.After shutdown,Check the panel terminal. Error 200 AFCI Fault 2.Restart inverter. 3.If error message still exists,contact manufacturer. DC Voltage High 1.Restart inverter.
  • Page 26: Manufacturer Warranty

    Manufacturer warranty Error Description Suggest Please refer to the warranty card. 1.Restart inverter. Error 413 IGBT drive fault 2.If error message still exists,contact manufacturer. 1.Restart inverter Decommissioning Error 414 EEPROM fault 2.If error message still exists, contact manufacturer. 15.1 Dismantling the Inverter I n t e r n a l p o w e r 1.Restart inverter.
  • Page 27: Eu Declaration Of Conformity

    5000TL3-XH 6000TL3-XH •2011/65/EU RoHS Directive and its amendment (EU)2015/863 Input data(DC) Shenzhen Growatt New Energy Co. Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned Max. recommended PV 6000W 8000W...
  • Page 28 Max. efficiency 98.30% Model Euro-eta 97.50% 7000TL3-XH 8000TL3-XH 9000TL3-XH 10KTL3-XH Specifications Protection devices Input data(DC) DC reverse-polarity Max. recommended PV 14000W 16000W 18000W 20000W protection power(for module STC) DC switch Max. DC voltage 1100V DC Surge protection typeII OPT Start voltage 160V Insulation resistance Nominal voltage...
  • Page 29: Compliance Certificates

    Contect us String Fuse protection String monitoring If you have technical questions about our products, please contact the Growatt New AFCI protection Energy Service Hotline. We need the following information to provide you with the necessary help: General data Ø...