Endress+Hauser Proline Promass I 100 Technical Information page 11

Coriolis
Hide thumbs Also See for Proline Promass I 100:
Table of Contents

Advertisement

Proline Promass I 100
Endress+Hauser
Current output
4-20 mA
Failure mode
HART
Device diagnostics
Pulse/frequency/switch output
Pulse output
Failure mode
Frequency output
Failure mode
Switch output
Failure mode
PROFIBUS DP
Status and alarm
messages
Modbus RS485
Failure mode
EtherNet/IP
Device diagnostics
Local display
Plain text display
With information on cause and remedial measures
Backlight
Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Selectable (as per NAMUR recommendation NE 43):
• Minimum value: 3.6 mA
• Maximum value: 22 mA
• Defined value: 3.59 to 22.5 mA
• Actual value
• Last valid value
Device condition can be read out via HART Command 48
Choose from:
• Actual value
• No pulses
Choose from:
• Actual value
• Defined value: 0 to 12 500 Hz
• 0 Hz
Choose from:
• Current status
• Open
• Closed
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Choose from:
• NaN value instead of current value
• Last valid value
Device condition can be read out in Input Assembly
11