Air Flow
Mellanox systems are offered with two air flow patterns:
• Power (rear) side inlet to connector side outlet - marked with blue power supplies/fans-
FRUs' handles, as shown in Figure 5.
• Connector (front) side inlet to power side outlet - marked with red power supplies/fans
FRUs' handles, as shown in figure Figure 6.
Table 6 provides an air flow color legend and respective OPN designations.
Table 6 - Air Flow Color Legend
8
Mellanox Technologies
All servers and systems in the same rack should be planned with the same airflow
direction.
All FRU components need to have the same air flow direction. A mismatch in the air
flow will affect the heat dissipation.
Direction
OPN
Designation
R
Connector side inlet to power side outlet.
Red latches are placed on the power inlet
side.
F
Power side inlet to connector side outlet.
Blue latches are placed on the power inlet
side.