Drilling Holes And Installing Expansion Bolts; Figure 2-9 Layout Of Installation Holes When A Battery Cabinet Is Configured - Huawei Airbridge BTS3606 Installation Manual

Cdma base station cabinet installation
Hide thumbs Also See for Airbridge BTS3606:
Table of Contents

Advertisement

Installation Manual – BTS3606A Cabinet Installation
Airbridge BTS3606&3606A CDMA Base Station
(1) Cement plinth
(3) Installation hole of the expansion bolt
(5) Front of the cabinet

Figure 2-9 Layout of installation holes when a battery cabinet is configured

2.3.4 Drilling Holes and Installing Expansion Bolts

Caution:
Bury the upper side of expansion tube in the ground. Otherwise, the cabinet may not
be able to sit firmly on the ground.
The depth of the hole must range from 52 mm (2.08 in.) to 60 mm (2.4 in.) (the
length of the expansion tube plus that of the drill bit). Otherwise, the expansion bolt
cannot be fastened.
All holes must have the same depth. Before measuring the depth of the hole,
remove the dust inside the hole to measure the net depth.
If the floor is too hard and smooth to settle the drill bit, punch a pit with a chisel to
help position the hole.
To drill holes and install expansion bolts, proceed as follows:
Chapter 2 Installing Cabinet Base or Channel Steel
Huawei Technologies Proprietary
2-8
(2) Outline of the battery cabinet
(4) Position of the BTS3606A cabinet