Note 7: Drives with an IGBT supply unit
If voltage is raised by the drive (this is a parameter selectable function), select the motor insulation
system according to the increased intermediate circuit DC voltage level, especially in the 500 V supply
voltage range.

Permanent magnet synchronous motor

Only one permanent magnet motor can be connected to the inverter output.
It is recommended to install a safety switch between the permanent magnet
synchronous motor and the drive output. The switch is needed to isolate the motor
during any maintenance work on the drive.

Supply connection

Disconnecting device (disconnecting means)

ACS800-01, ACS800-U1, ACS800-11, ACS800-U11, ACS800-02, ACS800-U2 without
enclosure extension, ACS800-04, ACS800-U4
Install a hand-operated input disconnecting device (disconnecting means) between
the AC power source and the drive. The disconnecting device must be of a type that
can be locked to the open position for installation and maintenance work.

ACS800-U2 with enclosure extension, ACS800-07 and ACS800-U7

These units are equipped with a hand-operated input disconnecting device
(disconnecting means) which isolates the drive and the motor from the AC power as
standard. The disconnecting device does not, however, isolate the input busbars
from the AC power. Therefore during installation and maintenance work on the drive,
the input cables and busbars must be isolated from the input power with a
disconnector at the distribution board or at the supplying transformer.
EU
To meet the European Union Directives, according to standard EN 60204-1, Safety
of Machinery, the disconnecting device must be one of the following types:
• switch-disconnector of utilization category AC-23B (EN 60947-3)
• disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
• circuit breaker suitable for isolation in accordance with EN 60947-2.
US
The disconnecting means must conform to the applicable safety regulations.

Fuses

See section
Thermal overload and short-circuit
protection.