58

Pulse encoder module cabling

Strain relief
with a cable tie

Fibre optic link

A DDCS fibre optic link is provided via the RDCO optional module for PC tools,
master/follower link, NDIO, NTAC, NAIO, AIMA I/O module adapter and fieldbus
adapter modules of type Nxxx. See RDCO User's Manual [3AFE64492209
(English)] for the connections.
When installing multiple modules on the same channel, connect them in a ring.

Warning sticker

There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the local language onto the cover of the drive module.
Electrical installation
Clamp as close to the terminals as
possible.
Alternative to a)
As short as
possible
1
2
3
4
Note1: If the encoder is of unisolated
type, ground the encoder cable at the
drive end only. If the encoder is
galvanically isolated from the motor
shaft and the stator frame, ground the
encoder cable shield at the drive and
a)
the encoder end.
Note 2: Twist the pair cable wires.
Note 3: The grounding wire of the outer
shield of the cable can alternatively be
connected to the SHLD terminal of the
RTAC module.