22 Safety instructions

Additional instructions for permanent magnet motor drives

Safety in installation, start-up, maintenance

These are additional warnings concerning permanent magnet motor drives. The other safety
instructions in this chapter are also valid.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
Do not do work on the drive when a rotating permanent magnet motor is connected to
it. A rotating permanent magnet motor energizes the drive including its input and output
power terminals.
Before installation, start-up and maintenance work on the drive:
Stop the drive.
Disconnect the motor from the drive with a safety switch or by other means.
If you cannot disconnect the motor, make sure that the motor cannot rotate during work.
Make sure that no other system, like hydraulic crawling drives, can rotate the motor
directly or through any mechanical connection like felt, nip, rope, etc.
Do the steps in section
Install temporary grounding to the drive output terminals (T1/U, T2/V, T3/W). Connect
the output terminals together as well as to the PE.
During the start up:
Make sure that the motor cannot run overspeed, for example, driven by the load. Motor
overspeed causes overvoltage that can damage or destroy the capacitors in the
intermediate circuit of the drive.

Safety in operation

WARNING!
Make sure that the motor cannot run overspeed, for example, driven by the load.
Motor overspeed causes overvoltage that can damage or destroy the capacitors
in the intermediate circuit of the drive.
Electrical safety precautions (page