2. Assembly Instructions
1) Remove length y of N, L conductor 35mm (1.38'')/PE conductor 40mm (1.57'')
sheath of AC cable terminal, length x about 14mm (0.55'') of the inner wrapper, then
dress the conductor terminals with ferrules or tin soldering.
2) Check that all parts of AC connector are present. Then slide hex nut onto the cable
and insert the cable end through clamp ring.
3) Insert the stripped N, L and PE conductor terminal to the appointed holes, use a
cross screwdriver to tighten it with tightening torque 1Nm.
24
NOTICE
Use 16-12AWG (1.5-4mm
wiring connections to Omnik inverter. Use only solid
wire or stranded wire.
2
) copper wire for all AC