Configuration and CFG-300 LCD Service Tool
Command Menu/FA-300 Config/Features/
6.Signal-Silence Inhibit timer
S i g - S i l . I n h i b i t T m r
[ X ] D I S A B L E
Command Menu/FA-300 Config/Features/
7. Aux. disconnect, disconnects
common alarm relay and common
supervisory relay
Aux Dis,Dis Alm&Spv
[X] DISABLE
Command Menu/FA-300 Config/Features/
8.Auto Signal Silence Timer
A u t o S i g - S i l . T i m e r
[ X ] D I S A B L E
Command Menu/FA-300 Config/Features/
9. Number of Remote
Annunciators or smart relays
N o . o f R e m o t e A n n u n .
[ X ] N O N E
Command Menu/FA-300 Config/Features/
10.Silence Alarm transmit
A l m . X m i t - S i l .
[ X ] D I S A B L E
Command Menu/FA-300 Config/Features/
11.AC power fail delay timer
A C P w r F a i l D l y T m r .
[ X ] N O N E
Note: Refer to How to Use the Keypad to Program the FA-300 on page 43 for detailed
instructions on making menu selections.
44
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
[ ] ENABLE
[X] DISABLE->Default
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
[X] NONE->Default
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
[X] DISABLE->Default
[ ] ENABLE
[X] NONE ->Default
[ ] 8 HRS
[ ] 18 HRS
Use this function to inhibit the
"SIGNAL SILENCE" switch for a
desired length of time. This time
period should expire before the
signals may be silenced.
According to the Canadian
National Building Code, this
timer should be set to one
minute.
If enabled, this function will
disconnect (when the Aux.
disconnect switch is pressed)
the Common Alarm relay and
Common Supervisory relay and
the PR-300 will not transmit a
supervisory or alarm event.
If disabled, the Aux disconnect
switch has no effect on the
Common Alarm relay, the
Common Supervisory relay and
the PR-300.
Use this function to determine
the time period for which the
indicating circuits will sound
before they are automatically
silenced. According to the
Canadian National Building
Code, this timer should not be
set to less than 20 minutes.
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays
can be used as long as the
number does not exceed 6. The
annunciators' addresses should
be linear: without gaps and in
sequence.
Use this function to allow the
alarm transmits and auxiliary
alarm relay to reset on "SIGNAL
SILENCE" rather than the
"RESET" switch.
Use this function to delay the
AC power fail trouble for the
programmed time period. If
disabled, the AC power fail is
reported right away.