How to Use the Keypad to Program the FA-300
1. Press MENU to enter the command menu.
2. Select a Command Menu option by pressing ENTER. The corresponding submenu will display.
3. Use the up and down arrow buttons to scroll through the submenu.
4. Press ENTER to select a submenu option.
5. Use the left or right arrow buttons to select/unselect an option (selected = "X"). Use the up and down arrows to
scroll through the different options.
6. Once you have made the correct selection, press ENTER to confirm the change. The display will return to the
submenu screen.
7. Press CANCEL to return to the previous menu.
Command Menu/FA-300 Config/Features/
1. Manual Signal Silence
M a n u a l S i g . S i l e n c e
[ X ] E N A B L E
Command Menu/FA-300 Config/Features/
2.Fire Drill
F i r e D r i l l
[ X ] E N A B L E
Command Menu/FA-300 Config/Features/
3.Output Circuit Correlation
O p t . C k t . C o r r .
[ X ] D I S A B L E
Command Menu/FA-300 Config/Features/
4.Waterflow/Sprinkler Retard
Operation
W a t e r f l o w / S p r k . R e t d
[ X ] D I S A B L E
Command Menu/FA-300 Config/Features/
5.Aux. disconnect, disconnects
Aux Alarm relay and all correlated
relays
Aux Dis Corr
[X] DISABLE
[X] ENABLE->Default
[ ] DISABLE
[X] ENABLE ->Default
[ ] DISABLE
[X] DISABLE->Default
[ ] ENABLE
[X] DISABL ->Default
[ ] ENABLE
[ ] ENABLE
[X] DISABLE->Default
FA-300 Series LED Version Installation and Operation Manual
Use this function to enable or
disable the SIGNAL SILENCE
operation from the front panel.
Use this function to enable or
disable the FIRE DRILL
operation.
If disabled, whatever correlation
is set in the correlation section
is effective. If enabled, all the
output circuits are correlated to
all the input circuits.
If disabled, all the initiating
circuits configured as water flow
or sprinkler act as non-verified
alarms. If enabled, retard
operation is performed for
initiating circuits configured as
water flow or sprinkler.
(See Water flow Alarm and
Sprinkler Alarm description)
In the default mode this function
will disconnect the Auxiliary
Alarm Relay when selected by
the Aux Disconnect button.
If enabled, this function will
disconnect the Auxiliary Alarm
Relay and all correlated relays
by pressing the Aux Disconnect
button. Correlated relays
include: RM312/RM306 relays,
SRM-312 relays.