Set Values For The Internal Heat Exchanger (Ihe) - Viessmann PLC VITOCAL 350-HT PRO Service Instructions For Contractors

Heat pump control unit
Table of Contents

Advertisement

Adjusting set values

Set values for the internal heat exchanger (IHE)

Launch with
"Menu"
"Set val."
"IHE"
Fig. 20
The following settings can be changed:
"Min sprhtg downstr.of IHE"
Set value for minimum compressor superheating
"Start opening angle"
Start opening angle of the 3-way valve
"Max. hot gas temp"
Hot gas temperature from which the 3-way valve
closes
"Max. suction gas temp"
Suction gas temperature from which the 3-way valve
closes
"Suction gas temp. increase if evap. temp. >="
Evaporation temperature from which the suction gas
temperature is increased to the "Max. suction gas
temp" value
(cont.)
"Suction gas temp increase if condensation temp
>="
Condensing temperature from which the suction gas
temperature is increased to the "Max. suction gas
temp" value
"Open IHE valve"
Speed at which the 3-way valve is opened
"Close IHE valve"
Speed at which the 3-way valve is closed
Configuring the system
27