Viessmann PLC VITOCAL 350-HT PRO Service Instructions For Contractors page 29

Heat pump control unit
Table of Contents

Advertisement

Communication
(cont.)
Terminal
Assignment
5
Termination
6
/RX/TX output
7
RX/TX output
8
Termination
Termination
The internal terminator must be activated if the heat
pump is connected to the start or end of the RS485
bus.
Two wire jumpers must be used for this purpose:
Connect terminals 5 and 6 to each other
Connect terminals 7 and 8 to each other
Transmission cables
Signals RX/TX and /RX/TX are required for transmis-
sion
RX/TX and /RX/TX are connected 1 to 1 with the
opposite side. GND must be connected to the data
cable screen on at least one side
For equipotential bonding, GND can be connected
on both sides.
In the case of potential differences, GND may be
connected on just one side. If the difference in poten-
tial is greater than 2 V, galvanic separation may be
required.
The data cable must be twisted and screened.
Modbus connection via Ethernet TCP
Modbus data transfer should always be carried out
via an Ethernet.
Installation of a separate data cable is not required.
RS485 converters for the PC connection are not
required.
Configuring the system
29