Kl400X - Technical Data - Beckhoff KL400 Series Documentation

Single-, dual and four-channel analog output terminals, (0v...10v)
Table of Contents

Advertisement

2.2

KL400x - technical data

Technical data
Number of outputs
Power supply for the electronics
Signal voltage
Load
Accuracy
Output error
Resolution
Electrical isolation
Conversion time
Current consumption from the K-bus
Bit width in the K-bus I/O
Configuration
Weight
Dimensions (W x H x D)
Mounting [} 11]
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity / emission
Protection class
Installation position
Approval
KL400x
KL4001
1
via the K-Bus
0 V...10 V
> 5 kΩ (short-circuit-proof)
± 0.5 LSB linearity error, ± 0.5 LSB offset error
< ± 0.10 % (at 0°C to +55°C)
< ± 0.75 % (when the extended temperature range is used)
12 bit
500 V (K-Bus / signal voltage)
~ 1.5 ms
typically 75 mA
Output: 1 x 16 bits of data (1 x
8 bit control/status optional)
No address or configuration settings
approx. 85 g
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
-25 °C to +60 °C (extended temperature range)
-40 °C to +85 °C
95 %, no condensation
conforms to EN 60068-2-6/EN 60068-2-27, see also Installation instructions for enhanced me-
chanical load capacity [} 15]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus, ATEX [} 22]
Version: 4.0
KL4002
2
Output: 2 x 16 bits of data (2
x 8 bit control/status optional)
Product overview
KL4004
4
< ±0.1 % of the end value
~ 2 ms
typically 85 mA
Output: 4 x 16 bits of data (4 x
8 bit control/status optional)
0 °C to + 55 °C
-25 °C to +85 °C
CE, cULus, ATEX [} 21]
9

Advertisement

Table of Contents
loading

Table of Contents