Download Print this page

Led Indication; Commissioning Test - ETC Echoflex Manual To Test And Configuration

Advertisement

I. 1 blink: disabled
II. 2 blinks: 5 minutes
III. 3 blinks: 10 minutes
IV. 4 blinks: 15 minutes
V. 5 blinks: 20 minutes (default)
VI. 6 blinks: 25 minutes
9. Tap until you reach the desired blink pattern
10. Press and hold 10 seconds to save the change or wait 60 seconds for the menu to time out (changes will not
be saved that way)

LED Indication

1. To enter the main test/config menu, press and hold TEACH/TEST button 6 seconds until:
a. occ/vac sensors except OWS:
b. OWS:
red/amber/green
2. Release button so:
a. occ/vac sensors except OWS:
b. OWS:
red/amber/green
3. Tap until the
red
4. Press and hold again for 6 seconds until the LEDs de-illuminate
5. Release button, the following LED will blink to indicate current setting:
a.
Red
LED: indication LED is active
b.
Green
LED: indication LED is inactive
6. Tap to select the preferred state
7. Press and hold 6 seconds to save the change or wait 60 seconds for the menu to time out (changes will not be
saved that way)

Commissioning Test

The commissioning test mode increases the 'heartbeat' of the sensor, or how often it sends its telegrams to allow for
quick feedback on light levels. This mode will increase the heartbeat to one telegram every 10 seconds and will last 5
minutes.
Make sure the sensor is fully charged or has a battery installed to run this test, as it requires
significantly more power consumption than regular usage.
1. To enter the main test/config menu, press and hold TEACH/TEST button 6 seconds until the
slowly
2. Release button so the
https://support.etcconnect.com/ETC/Architectural/Aero_and_EchoFlex/Aero_and_Echoflex_Sensors/Guide_to_Test_and_Co...
green
LEDs blink together
green
LEDs blink together
and
green
LEDs blink together
green
LED blinks faster
LED illuminates solid
LED illuminates solid
green
LED blinks
Updated: Fri, 17 Sep 2021 16:18:01 GMT