LG ARUM080LTE5 Engineering Product Data Book page 98

Table of Contents

Advertisement

Multi V 5
6. Electric Characteristics
Unit
Model
Hz
Volts
86 HP
60
380
88 HP
60
380
90 HP
60
380
92 HP
60
380
94 HP
60
380
96 HP
60
380
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit breaker
type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
' : 2 unit combination models
Power Supply
Voltage-range
MCA
Min.:342, Max.:418
172.7
Min.:342, Max.:418
172.7
Min.:342, Max.:418
190.0
Min.:342, Max.:418
191.8
Min.:342, Max.:418
192.7
Min.:342, Max.:418
196.4
TOCA
MFA
MSC
RLA(Cooling)
190.0
200
41.3
190.0
200
41.3
209.0
200
45.6
211.0
200
45.6
212.0
200
45.6
216.0
250
47.2
Symbols
MCA : Minimum Circuit Amperes (A)
TOCA : Total Over Current Amperes (A)
MFA : Maximum Fuse Amperes (A)
MSC : Maximum Starting Current (A)
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Outdoor Units
COMP
RLA(Heating)
81.7
98.0
85.0
102.4
84.0
101.6
86.8
106.1
91.1
109.5
94.0
112.8
OFM
kW
FLA
7.20
10.0
7.20
10.0
7.20
10.0
7.20
10.0
7.20
10.0
7.20
10.0
91