8. Electrical Wiring
1. Normal setting (Non-Zoning setting)
ex) Manual pipe detection of Valve #1, 6.
SW #1 On : Select Valve #1
SW #2 On : Select Valve #6
2. Zoning setting
Note
Use the Zoning Control when install two or more indoor units at 1 branch of HR Unit.
The indoor units controlled by Zoning Control can be selected collectively as the cooling/heating mode.
ex) Manual pipe detection of Valve #5 with three zoning indoor units, #6 without zoning unit.
Slave
SW #1 On : Select Valve #5
Slave
After selecting No.3 zoning
indoor unit, input the central
control address of indoor unit.
Slave
SW #2 On : Select Valve #6
Master
ON
OFF
SW01E
Input the central control
address of Indoor unit
Slave
ON
OFF
SW01E
Input the central control
address of Indoor unit
ON
OFF
SW01E
After selecting No.1 zoning
indoor unit, input the central
control address of indoor unit.
SW01C
SW02B
SW01B
Setting SW01C to '0'
ON
OFF
SW01E
Input the central control
address of Indoor unit
Master
SW02B
SW01B
SW #1 Off : Finish Valve #1
Slave
SW02B
SW01B
SW #2 Off : Finish Valve #6
Slave
0
SW01C
SW02B
SW01B
After selecting No.2 zoning
indoor unit, input the central
control address of indoor unit.
Slave
0
SW01C
SW #1 Off : Finish Valve #5
Slave
SW02B
SW01B
SW #2 Off : Finish Valve #6
Installation of Outdoor Units
Master
ON
OFF
SW01E
Slave
ON
OFF
SW01E
Slave
SW01C
SW02B
SW01B
Slave
ON
OFF
SW01E
Slave
ON
OFF
SW01E
45