LG ARUM080LTE5 Engineering Product Data Book page 725

Table of Contents

Advertisement

Multi V 5
7. Refrigerant piping system
7.1 Pipe Connection Method between outdoor unit/indoor unit
7.1.1 Heat Recovery System : 4 Outdoor Units
Example : 12 Indoor Units connected
ⓐ Outdoor Unit
ⓑ Y branch
ⓓ Indoor Units
E : Connection branch pipe between Outdoor units : ARCNB41
F : Connection branch pipe between Outdoor units : ARCNB31
G: Connection branch pipe between Outdoor units : ARCNB21
ⓗ Header
ⓛ HR Unit
H
• Case 1 ("a") : Maximum height is 30m(98.4ft) if you install with Y branch.
• Case 2 ("b") : Maximum height is 5m(16.4ft) in serial connection of HR units.
WARNING
Branch pipe can not be used after header
It is recommended that difference in length of the pipes connected to the indoor units (a~f) is minimized.
The large difference in pipe lengths, the more different performance between indoor units.
* : Serial connection of HR units : Capacity sum of indoor units ≤ 230 kBtu/h
If the large capacity indoor units (Over 5 HP; using overØ15.88/Ø9.52) are installed, it should be used
the Valve Group setting.
Refer to the HR unit PCB part for the valve group control setting.
Piping length from outdoor branch to outdoor unit ≤ 10m(32.8ft), equivalent length : max 13m(42.7ft)
(for 2 units combination or more)
14
Slave 3
Slave 2
Slave 1
G
F
E
1
a
2
b
C1
c
3
"a"
d
h
4
e
5
Master
ODU Capacity
Master ≥ Slave1 ≥ Slave 2 ≥ Slave 3
A
B
C3
C2
g
i
"b"
7
D
f
8
l
9
6
Installation of Outdoor Units
k
j
sealing
m
n
10
11
12