LG ARUM080LTE5 Engineering Product Data Book page 716

Table of Contents

Advertisement

Multi V 5
3. Installation Space
PRHR063 / PRHR083
160(6-5/16)
793(31-7/32)
No.
Part Name
1
Low pressure Gas pipe connection port
2
High pressure Gas pipe connection port
3
Liquid pipe connection port
4
Indoor unit Gas pipe connection port
5
Indoor unit Liquid pipe connection port
6
Control box
7
Hanger metal
Notice
1. Be sure to install the inspection door at the control box side.
2. If reducers are used, servicing space must be increased equal to reducer's dimension.
809(31-27/32)
7
Inspection door
(servicing space)
800(31-1/2)
2
3
1
160(6-5/16)
Ø28.58(1-1/8) Brazing connection
Ø22.2(7/8) Brazing connection
Ø15.88(5/8) Brazing connection
Ø15.88(5/8)~Ø12.7(1/2) Brazing connection
Ø9.52(3/8)~Ø6.35(1/4) Brazing connection
-
Suspension bolt M10 or M8
[Unit : mm(inch)]
300(11-13/16) more
300(11-13/16) more
(Servicing space)
300(11-13/16) more
(Servicing space)
6
126(4-31/32)
92
389
Description
PRHR063 / PRHR083
Installation of Outdoor Units
100 (3-15/16) more
(Serviceing space)
(Servicing space)
100 (3-15/16) more
(Serviceing space)
450(17-23/32) more
(Servicing space)
4
5
176
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents