8. Electrical Wiring
■ Automatic pipe detection(For Heat Recovery System)
1. Turn No.1 dip switch of SW02E of HR unit PCB off.
2. Confirm that the setting of No.2, 3, 4 of SW02E corresponds with the type of the valve connection.
3. Reset the power of HR unit PCB
4. Master outdoor unit PCB DIP switch on : No.5
5. Select the mode using '▶', '◀' Button : "Idu" Push the '●' button
6. Select the "Id 5" function using '▶', '◀' Button :"Ath" or "Atc" Push the '●' button.
Outdoor temperature is over 15°C(59°F) : "Ath" Using (If it fail, use "Atc")
Outdoor temperature is below 15°C(59°F) : "Atc" Using (If it fail, use "Ath")
7. Select the mode using '▶', '◀' Button : "Idu" Push the '●' button
8. Select the "Id 6" function using '▶', '◀' Button :"StA" Push the '●' button
9. System is operated after "88" is displayed on 7-SEG of the outdoor unit main PCB.
10.Pipe detection process is proceeded.
11.5~30 minutes are required depending on the number of the indoor units and outdoor temperature.
12.The number of the indoor units connected is displayed on 7-SEG of the outdoor unit main PCB for about 1 minute
For a HR unit, the number of the indoor units connected to each HR unit is displayed.
'200' is displayed in case of auto pipe detecting error, and auto pipe detection process is completed when
after "88" is disappeared.
CAUTION
Execute auto addressing and auto pipe detection again whenever the indoor PDB and HR unit PCB is
replaced.
– Operation error occurs unless power is supplied to the indoor and HR units.
Error No.200 occurs if the number of connected indoor units and that of scanned indoor units are
different.
If auto pipe detection process fails, complete it with manual pipe detection (see Manual pipe detection
part).
If auto pipe detection process is completed normally, manual pipe detection is not required.
If you want to do auto pipe detection again after auto pipe detection fails, do after reset of outdoor unit
by all means.
During 5 minutes after pipe detection is completed, do not turn off the main unit PCB to save the result
of pipe detection automatically.
48
Installation of Outdoor Units