LG ARUM080LTE5 Engineering Product Data Book page 732

Table of Contents

Advertisement

Multi V 5
7. Refrigerant piping system
■ Limits of pipe length and difference in height
Connection method
Longest pipe length (L)
: between Outdoor Unit and Indoor Unit
Max.pipe
Longest pipe equivalent length* (L)
length
: between Outdoor Unit and Indoor Unit
Longest pipe length after 1st branch (l)
Total pipe length
Difference in height (H)
: between Outdoor Unit and Indoor Unit
Max.difference
in height
Difference in height (h)
: between Indoor Unit and Indoor Unit
Note
* : Assume equivalent piping length of Y branch to be 0.5m (1.64ft), that of header to be 1m (3.28ft), calculation
purpose.
** : To apply Conditional Application
WARNING
When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A) must be
increased according to below table.
The equivalent length between outdoor unit and the farthest indoor unit is 90m (295ft) or more
(Liquid or Gas pipes are increased in accordance with below table)
The level difference (Outdoor unit ↔ Indoor unit) is 50m (164ft) or more (Only liquid pipe is increased)
■ Refrigerant pipe diameter from outdoor unit to first branch. (A)
Upward
Outdoor unit
Standard Pipe Diameter
total capacity
Liquid pipe
HP
[mm(inch)]
8
Ø 9.52(3/8)
10
Ø 9.52(3/8)
12 ~ 14
Ø 12.7(1/2)
16
Ø 12.7(1/2)
18 ~ 22
Ø 15.88(5/8)
24
Ø 15.88(5/8)
26 ~ 34
Ø 19.05(3/4)
36 ~ 60
Ø 19.05(3/4)
62 ~ 64
Ø 22.2(7/8)
66 ~ 96
Ø 22.2(7/8)
Note
* : If available on site, select pipe size from the pipe diameter table according to capacity.
Otherwise it doesn't need to be increased.
Model line up could be different in accordance with target region.
Y branch only
A+B+C+D+e ≤ 150m [492ft]
(200m [656ft]**)
175m [574ft]
(225m [738ft]**)
40m [131ft]
(90m [295ft]**)
1,000m [3,281ft]
110m [361ft]
40m [131ft]
When equivalent pipe length is 90m(295ft)
or more from ODU to farthest IDU
Gas pipe
Liquid pipe
[mm(inch)]
[mm(inch)]
Ø 19.05(3/4)
Ø 12.7(1/2)
Ø 22.2(7/8)
Ø 12.7(1/2)
Ø 28.58(1-1/8)
Ø 15.88(5/8)
Ø 28.58(1-1/8)
Ø 15.88(5/8)
Ø 28.58(1-1/8)
Ø 19.05(3/4)
Ø 34.9(1-3/8)
Ø 19.05(3/4)
Ø 34.9(1-3/8)
Ø 22.2(7/8)
Ø 41.3(1-5/8)
Ø 22.2(7/8)
Ø 41.3(1-5/8)
Ø 25.4(1) *
Ø 53.98(2-1/8)
Ø 25.4(1) *
Installation of Outdoor Units
Combination of Y
branch/header
A+B+b ≤ 150m [492ft] )
(200m [656ft]**)
A+C+e ≤ 150m [492ft]
(200m [656ft]**)
175m [574ft]
(225m [738ft]**)
40m [131ft]
(90m [295ft]**)
1,000m [3,281ft]
110m [361ft]
40m [131ft]
Increased Pipe Diameter
When level difference is 50m
Gas pipe
Liquid pipe
[mm(inch)]
[mm(inch)]
Ø 22.2(7/8)
Ø 12.7(1/2)
Ø 25.4(1) *
Ø 12.7(1/2)
not increased
Ø 15.88(5/8)
Ø 31.8(1-1/4) *
Ø 15.88(5/8)
Ø 31.8(1-1/4) *
Ø 19.05(3/4)
not increased
Ø 19.05(3/4)
Ø 38.1(1-1/2) *
Ø 22.2(7/8)
not increased
Ø 22.2(7/8)
Ø 53.98(2-1/8)
Ø 25.4(1) *
not increased
Ø 25.4(1) *
Header only
A+f ≤ 200m
[656ft]
225m [738ft]
40m [131ft]
1,000m [3,281ft]
110m [361ft]
40m [131ft]
or more
Gas pipe
[mm(inch)]
not increased
not increased
not increased
not increased
not increased
not increased
not increased
not increased
not increased
not increased
21