LG ARUM080LTE5 Engineering Product Data Book page 720

Table of Contents

Advertisement

Multi V 5
5. Installation
Install at places where it can endure the weight and vibration/noise of the outdoor unit.
The outdoor unit support block at the bottom shall have width of at least 100mm(3-15/16inch) under the units
legs before being fixed.
The outdoor unit support block hould have minimum height of 200mm(7-7/8inch).
Anchor bolts must be inserted at least 75mm(2-15/16inch).
Outdoor units
should not be
supported only by
the corner supports.
5.1 The location of the Anchor bolts
Chassis
UXA
UXB
Unit : mm(inch)
A [mm(inch)]
930(36-5/8)
1,240(48-13/16)
Installation of Outdoor Units
Center of the Unit
Center of the Unit
B [mm(inch)]
730(28-3/4)
1,040(40-15/16)
9