3. Installation Space
3.1 Individual Installation
■ Select installation location of the HR unit suitable for following conditions
Avoid a place where rain may enter since the HR unit is for indoor.
Sufficient service space must be obtained.
Refrigerant pipe must not exceed limited length.
Avoid a place subject to a strong radiation heat from other heat source.
Avoid a place where oil spattering, vapor spray or high frequency electric noise is expected.
Install the unit at a place in which it is not affected by operation noise. (Installation within cell such as meeting
room etc. may disturb business due to noise.)
Place where refrigerant piping, drain piping and electrical wiring works are easy.
PRHR023 / PRHR033 / PRHR043
150(5-29/32)
No.
Part Name
1
Low pressure Gas pipe connection port Ø28.58(1-1/8) Brazing connection
High pressure Gas pipe connection
2
port
3
Liquid pipe connection port
4
Indoor unit Gas pipe connection port
5
Indoor unit Liquid pipe connection port
6
Control box
7
Hanger metal
Notice
1. Be sure to install the inspection door at the control box side.
2. If reducers are used, servicing space must be increased equal to reducer's dimension.
4
500(19-11/16)
7
Inspection door
(servicing space)
500(19-11/16)
2
486(19-1/8)
150(5-29/32)
3
1
PRHR033 / PRHR043
Ø22.2(7/8) Brazing connection
Ø15.88(5/8) Brazing connection(PRHR043)
Ø12.7 Brazing connection(PRHR033)
Ø15.88(5/8)~Ø12.7(1/2) Brazing connection Ø15.88(5/8)~Ø12.7(1/2) Brazing connection
Ø9.52(3/8)~Ø6.35(1/4) Brazing connection
-
Suspension bolt M10 or M8
[Unit : mm(inch)]
300(11-13/16) more
300(11-13/16) more
(Servicing space)
300(11-13/16) more
(Servicing space)
126(4-31/32)
6
92(3-5/8)
389(15-5/16)
Description
Ø22.2(7/8) Brazing connection
Ø19.05(3/4) Brazing connection
Ø9.52(3/8) Brazing connection
Ø9.52(3/8)~Ø6.35(1/4) Brazing connection
-
Suspension bolt M10 or M8
Installation of Outdoor Units
100 (3-15/16) more
(Serviceing space)
(Servicing space)
100 (3-15/16) more
(Serviceing space)
450(17-23/32) more
(Servicing space)
4
5
176(6-15/16)
PRHR023