EXCLUSIVE X
The table shows the standard configurations allowed.
1 Bend 90° Ø 80
Air suction
4.5m pipe Ø80
1 Bend 90° Ø 80
4.5m pipe Ø80
Flue gas discharge
Reduction from Ø80 to Ø50 from Ø80 to Ø60
Flue base bend 90°, Ø50 or Ø60 or Ø80
For ducting pipe lengths see table
The boilers are factory set to:
CH rpm
6.200
7.300
7.300
Should greater lengths be required, compensate the pressure drop with an increase in the
r.p.m.of the fan, as shown in the adjustments table, to provide the rated heat input.
b
The minimum calibration should not be modified.
Table of adjustments INSIDE CHIMNEY PIPES
Fan rotations rpm
Pipes Ø50
CH
DHW
6.200
7.600
5
6.300
7.700
7*
6.400
7.800
9*
6.500
7.900
11*
6.600
8.000
13*
6.700
8.100
15*
6.800
8.200
17*
6.900
8.300
19*
7.000
8.400
22*
7.100
8.500
24*
7.300
7.800
2
7.400
7.900
3*
7.500
8.000
4*
7.600
8.100
6*
7.700
8.200
7*
7.800
8.300
9*
7.900
8.400
10*
8.000
8.500
12*
8.100
8.600
13*
8.200
8.700
15*
7.300
9.100
0
7.400
9.200
0*
7.500
9.300
1*
7.600
9.400
3*
7.700
9.500
4*
7.800
9.600
5*
7.900
9.700
7*
8.000
9.800
8*
8.100
9.900
9*
8.200
10.000
10*
(*)
Maximum length that can be installed ONLY with class H1 discharge pipes.
The Ø50 or Ø60 or Ø80 configurations contain Lab test data. In the event of installations
that differ from the indications in the "standard configurations" and "adjustments" tables,
refer to the equivalent linear lengths below.
b
In any case, the maximum lengths declared in the booklet are guaranteed, and it is
essential not to exceed them.
COMPONENT
Bend 45°
Bend 90°
Extension 0.5m
Extension 1.0m
Extension 2.0m
6
Max length pipes (m)
DHW rpm
Ø50
Ø60
7.600
5
18
7.800
2
11
9.100
0
7
twin flue pipe
Pipes Ø60
Pipes Ø80
∆P at boiler outlet
Maximum length (m)
18
98
23*
125*
28*
153*
33*
181*
38*
208*
43*
236*
48*
263*
53*
291*
58*
319*
63*
346*
11
57
15*
75*
19*
93*
22*
112*
26*
130*
30*
148*
33*
166*
37*
184*
40*
202*
44*
220*
7
42
10*
60*
13*
78*
16*
96*
19*
114*
23*
138*
26*
156*
29*
174*
32*
192*
35*
210*
Linear equivalent in metres Ø80 (m)
Ø 50
Ø 60
12.3
19.6
6.1
2.5
13.5
5.5
29.5
12
Ø80
98
4,5 m Ø 80 mm
57
42
2.8
Installation on collective flues in positive pressure (execpt for
40kW model)
Pa
174
The collective flue is a flue gas exhaust system suitable for collecting and expelling the
213
combustion products of several appliances installed on several floors of a building.
253
The positive pressure collective flues can only be used for type C condensing appliances.
Therefore the B53P/B23P configuration is forbidden. The installation of boilers under
292
collective pressure flues is allowed exclusively in G20. The boiler is sized to operate
332
correctly up to a maximum internal pressure of the flue no higher than the value of 25 Pa.
371
Check that the fan speed corresponds to what is shown in the "technical data" table.
410
Make sure that the air intake and exhaust pipes of the combustion products are watertight.
450
489
WARNINGS:
b
528
190
The appliances connected to a collective pipe must all be of the same type and have
229
equivalent combustion characteristics.
b
269
The number of devices connected to a positive pressure collective pipe is defined
308
by the flue designer.
348
The boiler is designed to be connected to a collective flue sized to operate in conditions
387
where the static pressure of the collective flue pipe can exceed the static pressure of the
426
collective air duct of 25 Pa in the condition in which n-1 boilers work at maximum rated heat
466
input and 1 boiler at the minimum rated heat input allowed by the controls.
505
b
544
The minimum permissible pressure difference between the flue gas outlet and the
196
combustion air inlet is -200 Pa (including - 100 Pa of wind pressure).
235
For both types of exhaust, further accessories are available (curves, extensions, terminals,
275
etc.) which make possible the flue gas exhaust configurations foreseen in the boiler booklet.
314
b
354
The pipes must be installed in such a way as to avoid condensation sticking which
393
would prevent the correct evacuation of the combustion products.
b
432
A data plate must be present at the connection point with the collective flue pipe.
472
The plate must include at least the following information:
511
- the collective flue is sized for boilers C(10) type
550
- the maximum permissible mass flow of the combustion products in kg/h
- the dimensions of the connection to the common pipes
- a warning concerning the openings for the air outlet and the entry of the combu-
stion products of the collective pressure pipe; these openings must be closed and
their tightness must be checked when the boiler is disconnected
- the name of the manufacturer of the collective smoke pipe or its identification
symbol.
b
See applicable legislation for the discharge of the combustion products as well as
local regulations.
b
The flue gas pipe must be suitably selected based on the parameters shown below.
5
ø 60-100
8
ø 80
ø 80/125
b
The terminal of the collective pipe must generate an upward air current.
b
Before attempting any operation, disconnect the appliance from the electrical supply.
b
Before assembling, lubricate the gaskets with a non-corrosive glide lubricant.
b
The flue gases discharge pipe should be inclined, if the pipe is horizontal, by 3°
towards the boiler.
b
The number and characteristics of the exhaust ventilation devices which are the real
characteristics of the flue itself.
b
The condensation can flow inside the boiler.
90° bends
Ø 80 mm
4,5 m Ø 80 mm
Ø 80-60 mm
or Ø 80-50 mm
reduction
maximum length
minimum length
4,5
4,5
4,5
chimney for ducting
Ø 50 mm or Ø 60 mm
or Ø 80 mm
90° bend
Ø 50 mm
Ø 60 mm
or Ø 80 mm
UM
0,5
m
0,5
m
0,5
m