Installation
Pressure test the supply line for leaks.
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
Failure to either disconnect or isolate the appliance
during pressure testing may result in regulator or valve
damages and void the warranty. Consult your dealer in
case of damages.
Pressure Test Points
The minimum supply pressure is given in the section
"Specifi cations" on page 6.
All piping and connections must be tested for leaks
after installation or servicing. All leaks must be
corrected immediately.
When testing for leaks:
• Make sure that the appliance is turned off .
• Open the manual shut-off valve.
• Test for leaks by applying a liquid detergent or soap
solution to all joints. Bubbles forming indicate a gas leak.
 WARNING
Never use an open flame to check
for leaks. Correct any leak detedted
immediately.
30
The pressure test tapping locations are shown in the
fi gure below. An internal regulator within the valve
controls the burner manifold pressure.
The correct pressure range is shown in the table in
section "Specifi cations" on page 6.
The pressure check should be made with the burner
alight and at its highest setting. See "Appendix A -
Lighting Instructions Plate" on page 62.
Manifold
Test
Pressure
Pressure Testing
Place the appliance in fi nal position
1. Taking great care not to cut your hands on the sheet
metal edges, place the appliance in its fi nal position
in the framing. Make sure that the unit is at the right
height with consideration to the height of the hearth or
combustible fl ooring.
2. Remove carrying handles on both side.
Complete Installation of HeatShift Kit
(required)
See "Appendix D - HeatShift® Installation" on page
71.
Gas Supply
Valve Inlet
Pressure
Manifold pressure
adjustment screw
located behind plastic
mushroom cap.