Minimum Vertical Vent-8" Vent - Valor LX2 2200KN Installation Manual

Direct vent zero clearance gas fireplace, 3-sides
Table of Contents

Advertisement

Planning
*
This is the minimum vent height when using 8-inch venting. If calculating the vent height using additional vent
lengths, subtract approximately 1-1/2 inch for each pipe joint. For example, an additional 12-inch pipe section
will add approximately 10-1/2 inches overall to this dimension.
Max. 24 " (610 mm)
length at this height
14
5" x 8" pipes
2"
(51 mm)
Required min.
clearance to
combustibles
Minimum Vertical Vent—8" Vent
8-1/2"
11-1/2"
(216 mm)
(292 mm)
5" x 8" elbow
directly on
appliance
5-1/4"
(133 mm)
17"
(432 mm)
11"
(279 mm)