To split the RAID

ATTENTION
1
Restart the CallPilot system and press Ctrl+M when prompted, to
enter the RAID setup utility during bootup.
2
From the Management menu select Objects > Physical Drive.
Result: A list of all drives organized per channel appears.
3
Select the A01- 2 drive using the cursor and press Enter.
4
Select Fail Drive.
Result: A warning message box appears. Ignore it and select Yes.
The drive status changes to FAILED. The alarm should start
beeping.
5
Repeat this process for the remaining two drives present on
Channel 2.
6
Press Esc three times to exit the Ctrl+M utility.
7
Reboot.
Result: The system reports that three drives are in critical mode
and starts beeping. This is OK; the system will still reboot.
Attention: The alarm can be silenced, but under no circumstances
should it be disabled. On the toolbar, select Objects
Alarm Control
1002rp Server Maintenance and Diagnostics
Because the 1002rp has three physical drives, the RAID
splitting must be done at the Ctrl+M utility level. Do not
perform this procedure using the Windows MegaRAID
console. There is a risk of database corruption.
Silence Alarm from the toolbar.