Outdoor Installation; Installations In The Commonwealth Of Massachusetts - Bradford White OmniTech BONH1250 Installation And Operation Instructions Manual

Category ii and iv venting with touchscreen controls
Hide thumbs Also See for OmniTech BONH1250:
Table of Contents

Advertisement

2.D Outdoor Installation
NOTE: Outdoor Installation of OMV's (volume water
heaters) is not permitted in Canada.
Precautions must be taken to prevent water in the heat
exchanger and condensate inside and outside of the
boiler from freezing. Damage due to freezing water or
condensate is not covered by the warranty. For units
installed outdoors, the minimum outdoor operating
temperature is 5F (-15C).
For proper operation in outdoor installations, the boiler
must be equipped with the inlet air and exhaust terminal
kits listed in Table 7. Additional instructions are supplied
with the terminal kits.
Size
Exhaust Vent
1250
CA016702
1500
1750
CA016802
2000
CA017602
2500
3000
CA017800
Table 7.
Outdoor Terminals
If installing outdoors in a location that may experience
freezing temperatures, provisions must be made to
protect the unit from freeze damage. Manufacturer
does not warranty damage caused by freezing
temperatures. The unit must not operate if the outdoor
temperature drops below 5F (-15C).
The outdoor vent terminal gets hot. This unit must be
installed in such a way as to reduce the risk of burns
from contact with the vent terminal.
Laars Part Number
Inlet Air
CA016900
CA017000
CA018100
WARNING
WARNING
2.E
Installations in the Commonwealth of
Massachusetts
In Massachusetts the following items are required if the
side-wall exhaust vent termination is less than seven
(7) feet above finished grade in the area of the venting,
including but not limited to decks and porches. (From
Massachusetts Rules and regulations 248 CMR 5.08.)
1. Installation of Carbon Monoxide Detectors
At the time of installation of the side-wall vented
gas fueled unit, the installing plumber or gasfitter
shall observe that a hard wired carbon monoxide
detector with an alarm battery back-up is installed on
the floor level where the gas unit is to be installed.
In addition, the installing plumber or gasfitter shall
observe that a battery operated or hard wired carbon
monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure
served by the side-wall horizontally vented gas fueled
equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed
professionals for installation of hard wired carbon
monoxide detectors.
a. In the event that the side-wall horizontally vented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide with alarm and
battery back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of the subdivision
cannot be met at the time of completion of installation,
the owner shall have a period of thirty (30) days
to comply with the above requirements, provided,
however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an
alarm be installed.
2. Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
3. Signage
A metal or plastic identification plate shall be
permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for
horizontally vented gas fueled heating unit or
equipment. The sign shall read, in print no less than
one-half (1/2) inch in size: "GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS."
4. Inspection
The state or local gas inspector of the side-wall
horizontally vented gas fueled unit shall not approve
the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248
CMR 5.08(2)(a) 1-4.
Page 23

Advertisement

Table of Contents
loading

Table of Contents