Section 13 Troubleshooting; Error Codes - Bradford White OmniTech BONH1250 Installation And Operation Instructions Manual

Category ii and iv venting with touchscreen controls
Hide thumbs Also See for OmniTech BONH1250:
Table of Contents

Advertisement

Page 120

SECTION 13 Troubleshooting

13.A Error Codes
Condition
Flow Switch
Low Water
Cut Off
Manual
Reset High
Limit
Auto Reset
High Limit
Gas Valve
Lockout
High Gas
Pressure
Low Gas
Pressure
Information
Insufficient flow at the outlet of the
boiler/heater
Auto-reset Condition
Annunciation – "Warning Flow
switch open" on Message Screen
Insufficient water level in the
boiler/heater heat exchanger.
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Low Water Cut Off
Outlet water temperature has
exceeded the manual reset high
limit setting
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Man Reset High Limit
Outlet water temperature has
exceeded the auto reset high limit
setting
Auto-reset Condition
Annunciation – "Warning High limit
auto error" on Message Screen
SV2 Gas Valve Lockout refer to gas
valve display for detailed diagnostic
information
Annunciation – on Navigation Bar
Lockout: Open Safety Chain
Annunciation – "Safety Chain open
SV2 Valve ILK" on Message Screen
Boiler
The high gas pressure switch has
tripped
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: High Gas Pressure
The low gas pressure switch has
tripped
Manual-reset Condition
Annunciation – on Navigation Bar
Corrective Action
Faulty boiler/heater pump –
replace pump.
Faulty pump contactor – replace
contactor.
Blown boiler/heater pump fuse –
replace fuse F14 on the control
board.
Reset the LWCO from the reset
button on the LWCO module.
Verify the system is full of water
and all air has been purged from
the system.
Check for loose jumpers if the
LWCO is not installed.
Verify the system is full of water
and all air has been purged from
the system.
Verify the boiler/heater is piped
properly into the heating system.
Check for proper pump
operations.
Check the manual reset high
limit set point.
Verify the system is full of water
and all air has been purged from
the system.
Verify the boiler/heater is piped
properly into the heating system.
Check for proper pump
operations.
Check the manual reset high
limit set point.
Refer to Gas valve Diagnostic
menu active lockouts for detailed
troubleshooting information.
Refer to Section 3 for Gas
Supply and Piping information.
Verify supply and manifold gas
pressures satisfy installation
requirements.
Refer to Section 3 for Gas
Supply and Piping information.