Appendix A - Display Tables - Carrier AquaSnap 30RAP011-060 Controls, Start-Up, Operation, Service, And Troubleshooting

Air-cooled chillers
Table of Contents

Advertisement

SUB-MODE
VIEW
RUN
HOUR
STRT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.
APPENDIX A — DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
ITEM
DISPLAY
EWT
XXX.X° F
LWT
XXX.X° F
SETP
XXX.X° F
CTPT
XXX.X° F
LOD.F
STAT
LD.PM
OCC
YES/NO
LS.AC
YES/NO
MODE
YES/NO
CAP
STGE
ALRM
TIME
XX.XX
MNTH
DATE
YEAR
C. TON
XXX.X TONS
HRS.U
XXXX HRS
STR.U
XXXX
HR.P1
XXXX HRS
HR.P2
XXXX HRS
HRS.A
XXXX HRS
HRS.B
XXXX HRS
HR.A1
XXXX HRS
HR.A2
XXXX HRS
HR.A3
XXXX HRS
HR.B1
XXXX HRS
HR.B2
XXXX HRS
HR.B3
XXXX HRS
ST.A1
XXXX
ST.A2
XXXX
ST.A3
XXXX
ST.B1
XXXX
ST.B2
XXXX
ST.B3
XXXX
ITEM DESCRIPTION
AUTO VIEW OF RUN STATUS
Entering Fluid Temp
Leaving Fluid Temp
Internal Active Setpoint
Control Point
XXX
Load/Unload Factor
Control Mode
Lead Pump
Occupied
Low Sound Active
Override Modes in Effect
XXX
Percent Total Capacity
X
Requested Stage
XXX
Current Alarms & Alerts
Time of Day
XX
Month of Year
XX
Day of Month
XX
Year of Century
Total Available Capacity
UNIT RUN HOUR AND START
Machine Operating Hours
Machine Starts
Pump 1 Run Hours
Pump 2 Run Hours
CIRC AND COMP RUN HOURS
Circuit A Run Hours
Circuit B Run Hours
Compressor A1 Run Hours
Compressor A2 Run Hours
Compressor A3 Run Hours
Compressor B1 Run Hours
Compressor B2 Run Hours
Compressor B3 Run Hours
COMPRESSOR STARTS
Compressor A1 Starts
Compressor A2 Starts
Compressor A3 Starts
Compressor B1 Starts
Compressor B2 Starts
Compressor B3 Starts
97
COMMENT
0=Service Test
1=Off Local
2=Off CCN
3=Off Time
4=Off Emrgcy
5=On Local
6=On CCN
7=On Time
8=Ht Enabled
9=Pump Delay
00:00-23:59
1 - 12 (1 = January,
2 = February, etc.)
01-31
See Note
See Note
See Note
See Note
See Note
See Note
See Note