Table D — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
WIRE TYPE
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
MS/TP
specifications.
NETWORK
24 AWG, single twisted shielded pair, low capacitance, CL2P,
(RS-485)
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
RNET
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
LOCAL ACCESS TO UPC OPEN CONTROLLER
The user can use a BACview
Virtual BACview software as a local user interface to an Open
controller. These items let the user access the controller network
information. These are accessory items and do not come with the
UPC Open controller.
The BACview
unit connects to the local access port on the UPC
6
Open controller. See Fig. F. The BACview software must be run-
ning on a laptop computer that is connected to the local access port
on the UPC Open controller. The laptop will require an additional
USB link cable for connection.
See the BACview Installation and User Guide for instructions on
connecting and using the BACview
To order a BACview
Handheld (BV6H), consult Commercial
6
Products i-Vu Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S PROP-
ERTIES
The UPC Open device and ComfortLink controller must be set to
the same CCN Address (Element) number and CCN Bus number.
APPENDIX D — BACNET COMMUNICATION OPTION (cont)
DESCRIPTION
handheld keypad display unit or the
6
device.
6
Fig. F — BACview
RECOMMENDED VENDORS AND PART NUMBERS
CONNECT AIR
INTERNATIONAL BELDEN RMCORP
W221P-22227
W241P-2000F
W184C-2099BLB
The factory default settings for CCN Element and CCN Bus num-
ber are 1 and 0 respectively.
If modifications to the default Element and Bus number are re-
quired, both the ComfortLink and UPC Open configurations must
be changed.
The following configurations are used to set the CCN Address and
Bus number in the ComfortLink controller. These configurations
can be changed using the scrolling marquee display or accessory
Navigator handheld device.
Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Address and
Bus Number in the UPC Open controller. These configurations
can be changed using the accessory BACview
Navigation: BACview→CCN
Home: Element Comm Stat
Element: 1
Bus: 0
Device Connection
6
130
CONTRACTORS
WIRE AND CABLE
25160PV
CLP0520LC
82841
25120-OR
6302UE
21450
CLP0442
display.