ALARM/
ALARM
ALERT
OR
DESCRIPTION
CODE
ALERT
Cooler Pump 2 Aux
T191
ALERT
Contacts Failed to Close
at Start-Up
Cooler Pump 1 Failed
T192
Alert
to Provide Flow at
Start-Up
Cooler Pump 2 Failed
T193
Alert
to Provide Flow at
Start-Up
Cooler Pump 1 Aux
Contacts Opened
T194
Alert
During Normal
Operation
Cooler Pump 2 Aux
Contacts Opened
T195
Alert
During Normal
Operation
Flow Lost While Pump 1
T196
Alert
Running
Flow Lost While Pump 2
T197
Alert
Running
Cooler Pump 1 Aux
A198
Alarm
Contacts Closed While
Pump Off
Cooler Pump 2 Aux
A199
Alert
Contacts Closed While
Pump Off
Pre-
Cooler Flow/Interlock
P200
Alert/
Contacts Failed to Close
/A200
Alarm
at Start-Up
Cooler Flow/Interlock
Pre-
P201
Contacts Opened
Alert/
/A201
During Normal
Alarm
Operation
Cooler Pump Interlock
A202
Alarm
Closed When Pump is
Off
Loss of Communication
T203
Alert
with Slave Chiller
Loss of Communication
T204
Alert
with Master Chiller
Master and Slave Chiller
T205
Alert
with Same Address
See Legend on page 82.
Table 44 — Alarm and Alert Codes (cont)
WHY WAS THIS
ALARM
GENERATED?
Pump 2 Auxiliary Contacts
did not close within
26 seconds after pump
was started
Pump 1 did not provide
flow to close flow switch
within 60 seconds
Pump 2 did not provide
flow to close flow switch
within 60 seconds
Pump 1 Auxiliary Contacts
open for 26 seconds after
initially made. All
compressors shut down.
Pump 1 turned off.
Pump 2 Auxiliary Contacts
open for 26 seconds after
initially made. All
compressors shut down.
Pump 2 turned off.
Cooler flow switch contacts
open for 3 seconds after
initially made
Cooler flow switch contacts
open for 3 seconds after
initially made
Pump 1 Auxiliary Contacts
closed for 2 minutes
when pump state is off
Pump 2 Auxiliary Contacts
closed for 2 minutes
when pump state is off
Cooler flow switch contacts
failed to close within
1 minute (if cooler pump
control is enabled) or
within 5 minutes (if cooler
pump control is not
enabled) after start-up
Flow switch opens for at
least 3 seconds after
being initially closed
If configured for cooler
pump control and flow
switch input is closed for
5 minutes while pump
output(s) are off
Master chiller MBB
loses communication
with slave chiller MBB
Slave chiller MBB loses
communication with
master chiller MBB
Master and slave chiller
have the same CCN
address (CCN.A)
81
ACTION TAKEN
BY CONTROL
METHOD
Pump 2 turned off.
Pump 1 will be started if
available.
Pump 1 turned off.
Pump 2 will be started
if available.
Pump 1 turned off.
Pump 2 will be started
if available.
Pump 2 will be started
if available. Chiller
allowed to run if
Pump 2 successfully
starts.
Pump 1 will be started
if available. Chiller
allowed to run if
Pump 1 successfully
starts.
All compressors
shut down. Pump 1
turned off. Pump 2 will
be started if available.
Chiller allowed to run if
Pump 2 successfully
starts and flow switch
is closed.
All compressors shut
down. Pump 2 turned
off. Pump 1 will be
started if available.
Chiller allowed to run if
Pump 1 successfully
starts and flow switch
is closed.
Chiller not allowed to
Manual when
start
aux contacts open
Chiller not allowed to
Manual when
start
aux contacts open
Chiller not allowed to
start. For models with
dual pumps, the
second pump will be
started if available
All compressors shut
down. For models with
Automatic (P201) or
dual pumps, the
Manual (A201)
second pump will be
started if available
Chiller not allowed to
Automatic when
start
aux contacts open
Dual chiller control
disabled. Chiller runs
Automatic
as a stand-alone
machine.
Dual chiller control
disabled. Chiller runs
Automatic
as a stand-alone
machine
Dual chiller routine
disabled. Master/slave
Automatic
run as stand-alone
chillers.
RESET
PROBABLE
CAUSE
Wiring error, faulty
Manual
contacts on pump
contactor
Wiring error, pump
circuit breaker
Manual
tripped, contactor
failure
Wiring error, pump
circuit breaker
Manual
tripped, contactor fail-
ure
Wiring error, faulty
Manual
contacts on pump
contactor
Wiring error, faulty
Manual
contacts on pump
contactor
Wiring error, pump
circuit breaker
Manual
tripped, contactor fail-
ure
Wiring error, pump
circuit breaker
Manual
tripped, contactor
failure
Wiring error, faulty
pump contactor
(welded contacts),
pump in hand position
Wiring error, faulty
pump contactor
(welded contacts),
pump in hand position
Wiring error, pump
circuit breaker
Manual
tripped, contactor
failure, faulty flow
switch or interlock
Cooler pump failure,
faulty flow switch or
interlock, pump circuit
breaker tripped
Wiring error, faulty
pump contactor
(welded contacts)
Wiring error, faulty
wiring, failed Slave
chiller MBB module,
power loss at slave
chiller, wrong slave
address.
Wiring error, faulty
wiring, failed master
chiller MBB module,
power loss at Master
chiller.
CCN Address for both
chillers is the same.
Must be different.
Check CCN.A under
the OPT2 sub-mode
in Configuration at
both chillers.