Carrier AquaSnap 30RAP011-060 Controls, Start-Up, Operation, Service, And Troubleshooting page 45

Air-cooled chillers
Table of Contents

Advertisement

Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont)
SUB-MODE
ITEM
LLBL
LLBL
LLBD
RSET
(CONT)
LLDY
LLDY
PARA
NOTES:
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occu-
pancy or 3-CCN.
2. Parallel Configuration (PARA) cannot be changed.
KEYPAD ENTRY
DISPLAY
0
ENTER
0
ENTER
2
2
ENTER
ESCAPE
LLBL
LLBD
168
ENTER
LLBD
ESCAPE
LLDY
5
ENTER
5
ENTER
10
10
ENTER
LLDY
ESCAPE
RSET
ESCAPE
YES
ENTER
ITEM EXPANSION
LEAD/LAG BALANCE SELECT
LEAD/LAG BALANCE DELTA
LEAD/LAG BALANCE DELTA
LAG START DELAY
LAG START DELAY
45
COMMENTS
SCROLLING STOPS
VALUE FLASHES
SELECT 2 - Automatic
CHANGE ACCEPTED
DEFAULT 168
SCROLLING STOPS
VALUE FLASHES
SELECT 10
CHANGE ACCEPTED
MASTER COMPLETE