Carrier AquaSnap 30RAP011-060 Controls, Start-Up, Operation, Service, And Troubleshooting page 48

Air-cooled chillers
Table of Contents

Advertisement

MODE
KEYPAD
(RED LED)
ENTRY
ENTER
CONFIGURATION
*4 items skipped in this example.
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 34 — Space Temperature Reset
Table 26 — Configuring Return Fluid Temperature Reset
KEYPAD
SUB-MODE
ITEM
ENTRY
DISP
ENTER
UNIT
ENTER
OPT1
ENTER
OPT2
ENTER
CCN
EXV.A
EXV.B
MM
RSET
CRST
ENTER
RT.NO*
RT.F
RT.DG
ITEM
DISPLAY
EXPANSION
3
COOLING RESET TYPE
RETURN FLUID - NO
10.0 F
RESET TEMP
RETURN FLUID - FULL
2.0 F
RESET TEMP
RETURN - DEGREES
5.0 F
RESET
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 35 — Outdoor-Air Temperature Reset
48
COMMENT
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to LVT-9,8)
2 = Outdoor-Air Temperature
3 = Return Fluid
4 = Space Temperature
(Connect to LVT-22,23)
Default: 10.0 F (5.6 C)
Range: 0° to10 F COOLER T
(0 to 5.6 C)
Default: 0 F (0 C)
Range: 0° to 30 F COOLER T
(0 to 16.7 C)
Default: 0 F (0 C)
Range: –30 to 30°F (–16.7 to 16.7 C)