1MRS756711 D
IEC 61850 name
.Op.phsC
.Str.general
.Str.phsA
.Str.phsB
.Str.phsC
2.3.1.33
Table 36:
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
IEC 61850 name
CTRL.LLN0
.Loc.stVal
2.3.1.34
Table 37:
LD0.LLN0 Settings supervision
IEC 61850 name
LD0.LLN0
.SetChg.stVal
.SetSeld.stVal
2.3.1.35
Table 38:
LD0.MVGAPC1 Multipurpose binary inputs (1)
IEC 61850 name
LD0.MVGAPC1
.Q1.stVal
.Q2.stVal
.Q3.stVal
.Q4.stVal
.Q5.stVal
.Q6.stVal
.Q7.stVal
.Q8.stVal
REF615
Point List Manual
SA name
-
-
-
-
-
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
SA name
LD0.LLN0 Settings supervision
SA name
-
-
LD0.MVGAPC1 Multipurpose binary inputs (1)
SA name
-
-
-
-
-
-
-
-
Description
-phsC Operate
-General Start
-phsA Start
-phsB Start
-phsC Start
Description
Remote/Local state
Description
Settings changed
Settings reserved
Description
Input 1 signal
Input 2 signal
Input 3 signal
Input 4 signal
Input 5 signal
Input 6 signal
Input 7 signal
Input 8 signal
Section 2
DNP3 data mappings
Values
1=Operate
1=Start
1=Start
1=Start
1=Start
Values
0/1=Rem/Loc
Values
1=Changed
1=Reserved
Values
0/1=Off/On
0/1=Off/On
0/1=Off/On
0/1=Off/On
0/1=Off/On
0/1=Off/On
0/1=Off/On
0/1=Off/On
25